7. Putting Unit into Service
The following procedure must be adhered to when putting the relay into service after finishing
commissioning or maintenance tests.
Check that all external connections are correct.
Check the setting of all elements, recordings and clock are correct.
In particular, when settings are changed temporarily for testing, be sure to restore them.
Clear any unnecessary records on events which are recorded during the tests.
Check that the green "IN SERVICE" LED is lit and no other LEDs are lit on the front panel.