Monobloc Outdoor Unit Service Manual
21
6. Key electric component rating
6.1.
Monobloc outdoor unit
No
Component Name
Model
Type
Rating
CP1701
CP2101
Refrigeration
1
DC twin rotary compressor
O
-
DA422A3F-27M
Winding resistance:
0.79 Ω (20°C)
O
DA550A3F-11M
Winding resistance: 0.56
Ω (20°C)
2
Accumulator
O
O
Vol. = 5.8 l
3
Receiver
O
O
Vol. = 5.75 l
4
2 way solenoid valve
O
O
Body: VPV-603D
Coil: VPV-MOAJ524C0
Rated volt: AC 220~240V 50Hz
Tolerance (V): -15% ~ +10%
Power: 6 ± 0.5W
Rated (A): 45 ± 4mA
5
4 way reversing valve
O
-
Body: 0150412H66
Coil: 00PPG000523900A
Rated volt: AC 220~240V 50Hz
Tolerance (V): -15% ~ +10%
Power: 6 ± 0.5W
6
-
O
Body: 00PPG000505700
Coil: 00PPG000523900
Rated volt: AC 220~240V 50Hz
Tolerance (V): -15% ~ +10%
Power: 6 ± 0.5W
7
Pulse modulating valve
O
-
Body: 0150420H18
Coil: 00PPG000506800A
Rated volt: DC 12V ± 10%
Rated (A): 0.26A/phase (20°C)
Coil
Ω: 46 ± 3Ω
8
-
O
Body: 00PPG000506700A
Coil: 00PPG000506800A
Qty. = 2 (parallel)
Rated volt: DC 12V ± 10%
Rated (A): 0.26A/phase (20°C)
Coil
Ω: 46 ± 3Ω
9
Fan motor
O
O
B036870H01
Qty = 2
Water
10
Water flow switch
O
O
Sika
Operating flow rate “ON” = 0.28 l/sec
Operating flow rate “OFF” = 0.24 l/sec
Electrical
11
Terminal block TB X2
O
O
Sensors
12
Discharge temperature sensor (td)
O
O
45k
Ω (25°C) / 7kΩ (75°C)
13
Heat exchanger sensor 1 (te)
O
O
10k
Ω (25°C)
14
Heat exchanger sensor 2 (tl)
O
O
45k
Ω (25°C) / 7kΩ (75°C)
15
Outdoor air temperature sensor (to)
O
O
10k
Ω (25°C)
16
Refrigerant sensor (tr)
O
O
10k
Ω (25°C)
17
Suction temperature sensor (ts)
O
O
10k
Ω (25°C)
18
Entering water temperature sensor
EWT (RT2)
O
O
5k
Ω (25°C)
19
Leaving water temperature sensor
LWT (RT1)
O
O
5k
Ω (25°C)
20
Low pressure sensor (BP1 / LP)
O
O
NSK-BC010I
0 - 10Bar (0.5 – 4.5V)
21
Paddle flow switch
OP
OP
22
Water pump (optional)
OP
OP
6.2.
ESTIA hot water cylinder
No
Component Name
Model
Rating
1501
CSHM3
2101
CSHM3
3001
CSHM3
1
Hot water cylinder heater
O
O
O
AC230V 2.75kW
2
Hot water cylinder temperature
sensor (TTW)
O
O
O
10k
Ω (25°C)
3
Thermal cut out
O
O
O
Operating temperature:
Manual reset 82°C +3K/-2K
Содержание Estia RUA-CP1701H
Страница 15: ...Monobloc Outdoor Unit Service Manual 14 4 3 ESTIA hot water cylinder ...
Страница 18: ...Monobloc Outdoor Unit Service Manual 17 5 1 3 Wiring Diagram Sheet 6 ...
Страница 19: ...Monobloc Outdoor Unit Service Manual 18 5 1 4 Wiring Diagram Sheet 7 ...
Страница 20: ...Monobloc Outdoor Unit Service Manual 19 5 1 5 Wiring Diagram Sheet 8 ...
Страница 21: ...Monobloc Outdoor Unit Service Manual 20 5 2 General electrical connection 5 3 ESTIA hot water cylinder ...
Страница 24: ...Monobloc Outdoor Unit Service Manual 23 6 3 3 MCC 1599 interface PCB 6 3 4 MCC 1600 noise filter ...
Страница 28: ...Monobloc Outdoor Unit Service Manual 27 7 2 Refrigeration cycle system diagram Pumpless models ...
Страница 29: ...Monobloc Outdoor Unit Service Manual 28 Variable fixed speed hydraulic models ...
Страница 70: ...Monobloc Outdoor Unit Service Manual 69 ...
Страница 75: ...Monobloc Outdoor Unit Service Manual 74 ...
Страница 157: ...Monobloc Outdoor Unit Service Manual 156 16 2 21kW Fixed Speed Variable Speed Pumpless ...
Страница 160: ...Monobloc Outdoor Unit Service Manual 159 ...
Страница 161: ...Monobloc Outdoor Unit Service Manual 160 ...
Страница 162: ......
Страница 163: ......
Страница 164: ...TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel France 1402410501R03 ...