manualshive.com logo in svg
background image

SMART MANAGER

Model name:

BMS-SM1280HTLE

Installation Manual

• Save These Instructions!

ENGLISH

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание BMS-SM1280HTLE

Страница 1: ...SMART MANAGER Model name BMS SM1280HTLE Installation Manual Save These Instructions ENGLISH AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 2: ...itches for Setting 12 6 Central Control Address Group Number Setting 16 7 Mode Setting for Smart Manager 19 8 Zone Setting 20 9 Changing Return Back Time Temperature Settings 21 10 Test Run 22 Thank you very much for purchasing this TOSHIBA Smart Manager Please read this manual carefully beforehand for proper installation of the Smart Manager AMP Air Conditioning www ampair co uk sales ampair co u...

Страница 3: ...ment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actual contents of the obligation indicated by a picture o...

Страница 4: ...consumption 7W Connectable unit number Indoor unit Up to 128 units Line1 Up to 64 units Line2 Up to 64 units Energy monitoring interface Up to 4 units Digital input output interface Up to 4 units Operating temperature humidity 0 o C to 40 o C 10 to 90 RH no condensation Dimension 120 H x 180 W x 64 D mm 114 H x 177 W x 50 D mm Mass 0 8 kg 0 9 kg 180 120 19 140 45 90 AMP Air Conditioning www ampair...

Страница 5: ...er 7 Screws 8 4 for fixing the central controller 4 for fixing the power unit 8 Brackets 2 For combining the central controller and power unit 9 Bracket screws 4 For combining the central controller and power unit No Line Type Wire size Length 1 For TCC LINK 2 core shield wire 1 25mm 1000m max total length including 2 00mm 2000m max air conditioner area 2 For RS 485 2 core shield wire 1 25mm 500m ...

Страница 6: ...a noise source Installing central controller 8 5 5Ø 8 5 155 142 172 17 9 76 12 7 106 6 108 65 Panel Base Central Controller box Fix the panel by hooking the nails This hole is provided for penetration of the Central Controller box fixing screw Insert a flat blade screwdriver or the like into the right and left grooves at the bottom of the panel and then carefully detach the panel Dimensions of uni...

Страница 7: ...ing places Humid or wet place Dusty place Place exposed to direct sunlight Place where there is a TV set or radio within one meter Place exposed to rain outdoors under eaves etc Installation Space and Maintenance Space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be adjacent to surrounding objects No go...

Страница 8: ...power unit using the supplied brackets as follows in order to control them as one unit Combination method Power unit Bracket Panel Fix the brackets and the central controller box together using the screws on the box Fix the power unit to the brackets using the bracket screws AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 9: ...e careful when connecting the wire The TCC LINK communication cable must be earthed on the air conditioner Do not connect the shield wire to the terminal block It should be open and insulated central controller power cable Connect the earth wire securely to the earth terminal on the unit Fix the cable securely with the clamp Power cable Power supply 220 240V AC Connect the shield wire of the RS 48...

Страница 10: ...contacts must be compatible with minimal current DC5V 3mA Pulse width 300 ms or more Wiring length 100 m or less N L 35 55 35 55 35 6 Length of stripped power cable Length of stripped TCC LINK communication cable Length of stripped digital Input Output communication wire Attach the supplied clamp filter to the LAN cable Wind the LAN cable around the clamp filter as shown below when attaching the f...

Страница 11: ...door units respectively See 6 Central Control Address Group Number Setting A smart manager has two TCC LINK communication lines line 1 and line 2 Each line can contain up to 64 groups and 64 zones and 128 groups and 128 zones can be set in total A zone is a control unit consisting of a combination of any indoor units You can make up to 64 zones pairing any of up to 64 groups For setting zones see ...

Страница 12: ...alram Normal Fire alram Normal DS25 ON 3 Must be set to OFF DS24 ON OFF 4 Must be set to OFF LINE 2 LINE 1 OFF ON Buzzer Control group Selection Line OFF ON Indicate DS23 DS24 ALL groups group 1 16 group 17 32 group 33 48 group 49 64 Control groups Selection DS23 ON OFF SUB MAIN RCU CENTRAL SUB MAIN INHIBIT PERMIT Central Individual Sys con Central RCU change Central Control State for Weekly timer...

Страница 13: ...2 ON 3 ON Group 33 48 ON 4 ON Group 49 64 ON 5 ON 6 Central control remote controller mode selection OFF Central control mode ON Remote controller mode Central control mode The smart manager is used as the central control device Remote controller mode The smart manager is used as the remote controller 7 Central control Main Sub selection OFF Main ON Sub This setting is required when multiple Smart...

Страница 14: ...AL 1 OFF ON OFF 4 All OFF and all indoor units to be CENTRAL 1 ON ON OFF 5 All indoor units CENTRAL 2 OFF OFF ON 6 All OFF and all indoor units to be CENTRAL 2 ON OFF ON 6 Control group selection enable OFF Normal mode ON Control group selection Set this bit to ON when the control group selection is used To use the control group selection set DS23 2 to 5 and DS24 5 to 6 For details see 7 Mode Sett...

Страница 15: ...ed to fire alarm COM DI DI3 COM DI DI3 Fire alarm Normal COM DI DI3 COM DI DI3 Fire alarm Normal Factory setting All OFF 2 Synchronization of zone setting data OFF With synchronization ON Without synchronization This bit specifies whether to perform synchronous communication of zone setting data between Smart Managers When this bit is set to ON without synchronization synchronous communication is ...

Страница 16: ...er unit to ON only for one system and to OFF for others The location of SW30 is shown in the wiring diagram supplied with the outdoor unit Setting central control addresses group numbers Use manual setting from wired remote controller manual setting or automatic setting to set central control addresses A Manual setting from wired remote controller Set central control addresses group numbers from a...

Страница 17: ...g C Automatic setting Set central control addresses automatically from the Smart Manager Central control addresses are set automatically in ascending order of unit number 1 Press the button and ZONE button simultaneously for at least 4 seconds CODE No C1 flashes 2 Press the SET TEMP or button to change the CODE No to C2 3 Press the button Central control addresses are automatically registered This...

Страница 18: ... with the SET TEMP or button 2 Press the button 3 The number of group in which the error has been detected flashes Select the flashing group number to be corrected with the GROUP or button 4 Press the button to clear the set incorrect central control address After that set a correct central control address 5 Press the button to terminate the duplicate address correction AMP Air Conditioning www am...

Страница 19: ...de is available only for one line Multiple group ranges can be specified by the control group setting OFF side Central control mode This Smart Manager is used as a central control unit Settings with the remote controller are inhibited by the setting of the Smart Manager ON side Remote control mode This Smart Manager is used as a remote controller Settings with the Smart Manager are inhibited by th...

Страница 20: ... registered in the zone light up 3 Change registration of groups in a zone Register groups in a zone 1 Select the group number to be set with the GROUP or button Pressing the SET TEMP or button skips the group number by 16 or by 16 2 Press the button The registered group number stops flashing and lights still 3 Pressing the button restores the state before the button is pressed 4 To continue regis...

Страница 21: ...buttons to set the time setting to 045 4 Press the button to determine the data and CODE No stop flashing and stay lit To continuously change other settings repeat steps 2 to 4 above 5 Determine the change Press the button to write the updated data in the memory of the remote controller When the data has completely been written in the memory the CODE No setting change mode is exited NOTE Setting a...

Страница 22: ... the group number count displayed on the Smart Manager 4 When these numbers are identical there is no problem If they differ set central control addresses again according to Central Control Address Group Number Setting Also make sure that there is no incorrect wiring Conducting a Test Run for Air Conditioners 1 Press the button for at least 4 seconds The TEST indication lights in the test run mode...

Страница 23: ...Smart Manager Installation Manual EN 23 EN AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 24: ...DE93919101 AMP Air Conditioning www ampair co uk sales ampair co uk ...