Central Control Device (Touch Screen Controller)
Installation Manual
• Save These Instructions!
ENGLISH
Model name:
BMS-CT2560U-E(BMS-CT1280TU)(BMS-CT2560U-TR)
For commercial use
Страница 1: ...Central Control Device Touch Screen Controller Installation Manual Save These Instructions ENGLISH Model name BMS CT2560U E BMS CT1280TU BMS CT2560U TR For commercial use ...
Страница 2: ...lation of Main Unit Box and Panel 8 3 1 1 When Installing from the Front 8 3 1 2 When Installing from the Rear 9 3 2 Attaching the Power Adapter 10 3 3 Power Signal and Earth Line Connections 11 Thank you for purchasing the system controller Please read this installation manual carefully before installation and perform the work only in the correct manner ...
Страница 3: ...hich do not require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actu...
Страница 4: ...d cables and connect them securely and do not subject connecting terminals to external force Doing so may result in broken cables excessive heat or fire Always install a circuit breaker on the primary side of the power supply Clean the touch panel by wiping with an eyeglasses cleaner or other soft cloth To remove oil based ink wipe with a cloth that has been moistened with a neutral detergent and ...
Страница 5: ...units LINK2 terminal maximum 128 units ON OFF unit Maximum 60 units Power meter interface Up to 4 units Digital I O interface Up to 4 units Communication ports RS 485 port 1 LAN port 1 USB port USB memory stick connection port 2 External contact input 8 inputs External contact output 4 outputs Operating temperature humidity range 0 C to 40 C 10 to 90 RH no condensation Dimensions H136 mm W205 mm D...
Страница 6: ...N Can be connected to a PC via LAN communication and monitored and controlled Ø15 0 29 6 0 5 1500 0 20 0 30 5 110 0 0 5 62 0 0 5 Ø5 5 0 1 Ø2 5 0 1 0 0 5 0 15 0 0 Ø12 0 0 5 6 5 0 3 33 0 0 5 7 5 0 3 FERRITE AS REQUIRED WIRE NO 1185 GAUGE 16AWG BLACK SPEC LABEL LED 31 5 MAX COM DI 4 COM DI 3 COM DI 2 COM DI 1 LINK1 Uh INPUT LINK2 Uh RS 485 U3 U4 U3 U4 FG B A COM DI 8 COM DI 7 COM DI 6 COM DI 5 INPUT ...
Страница 7: ...al 1 5 Fixing screw 4 Fixing screw M4 12 for attaching the main unit from the front 6 Fixing screw 4 Fixing screw M3 8 for attaching the main unit from the rear 7 Closed end connector 2 RS 485 cable crimp connector 8 Cable tie 2 For fixing the power adapter 9 Double sided tape 1 For fixing the power adapter No Wiring Wire type wire diameter wire length 1 For LINK terminal Refer to Design of Contro...
Страница 8: ... AC adapter and LAN cable to the main unit 2 Fit the main unit on to the wall and switch board 3 Insert a flat head screwdriver etc into the groove on the left and right of the bottom of the panel There will be a snapping sound and the panel will come off REQUIREMENT Just insert the screwdriver and do not twist it To prevent the panel from falling support it during removal 4 Fix the 4 main unit sc...
Страница 9: ...l installation work 1 Drill four Ø4 holes in the switchboard wall etc 2 Fit the main unit on the switch board wall etc 3 Fix from the rear of the main unit Please use the supplied M3 8 screws 4 Connect the TU2C LINK cable AC adapter and LAN cable to the main unit 5 When installation is completed peel off the transparent film Main unit box Panel 183 120 100 133 20 93 53 202 190 4 5 8 5 8 20 20 Syst...
Страница 10: ...nd and double sided tape REQUIREMENT Do not install in the following locations Locations with high humidity or water Dusty locations Locations in direct sunlight and locations subject to high temperatures Locations within 1 m from televisions or radios Outdoors under awnings or other locations exposed to rain and dew Installation allowed Installation not allowed Install so that the power cable tha...
Страница 11: ...oor unit Remote controller LINK 2 RS 485 signal line LINK1 and LINK2 terminals do not have polarity The RS 485 cable has polarity A B It will not work correctly if it is connected with incorrect polarity Connect the shielded wire of the RS 485 signal line to the FG terminal block Connection with power meter interface digital I O interface sold separately Power connector DC 12 V Connect the shield ...
Страница 12: ... Shield grounding process RS 485 cable wire shielded wire Connect to the FG terminal block TU2C LINK communication line shielded wire When using the system controller with one unit open the shielded wire of the TU2C LINK communication line and perform insulation processing When using the system controller with multiple units connect the shield of the TU2C LINK communication line to the closed end ...
Страница 13: ...series TCC LINK other than U series Outdoor unit Other than on the left MMY MAP MCY MAP etc Indoor unit Other than on the left MM AP etc Wired remote controller Other than on the left Wireless remote controller receiver Other than on the left System controller Other than on the left U series outdoor units Super Multi u series MMY MUP Outdoor units other than U series Super Module Multi i series MM...
Страница 14: ...on error System diagram The wiring specifications in the system diagram above are the same even when the indoor unit or remote controller are other than the U series Item Communication line Central control wiring Uh line Wire diameter 1 0 to 1 5 mm2 up to 1000 m 2 0 mm2 up to 2000 m Wire type 2 core non polar Wire types that can be used Shielded wire U3 U4 LINK Uh U6 U4 U1 U2 Uv A B U6 U4 U1 U2 Uv...
Страница 15: ...he indoor unit or remote controller are other than the U series Item Communication line Control wiring between indoor and outdoor units and central control wiring Wire diameter 1 25 mm2 up to 1000 m 2 0 mm2 up to 2000 m Wire type 2 core non polar Wire types that can be used Shielded wire U2 U4 U3 U4 U3 U4 U6 U4 U1 Uv Uv Uv Uv U2 A B U6 U4 U1 U2 A B U6 U4 U1 U2 A B U6 U4 U1 U2 A B U1 U3 U2 U5 U6 U3...
Страница 16: ...meters may cause a communication error System diagram The wiring specifications in the system diagram above are the same even when the indoor unit or remote controller are other than the U series Item Communication line Central control wiring Uh line Wire diameter 1 25 mm2 up to 1000 m 2 0 mm2 up to 2000 m Wire type 2 core non polar Wire types that can be used Shielded wire U 2 U 4 U 3 U 4 U3 U4 U...
Страница 17: ...ltage current 24 V DC 35 mA or less Wiring length Within 100 m If you want to use relays please refer to page 18 Control input Electric energy pulse Wiring length Within 100m Control input No voltage contact A Pulse or static Electric energy pulse No voltage A Pulse Pulse width 50 msec or more No voltage contact compatible with a very small current 3 mA or less DC5 V DO1 Output common DO2 Output c...
Страница 18: ... units other than the U Series are connected each line has 64 groups LINK1 and LINK2 together have 128 groups and 128 zones When an outdoor unit other than the U series is connected to either line it is set when an outdoor unit other than the U series is connected on both lines Interface connection Connect the power meter interface and the digital I O interface to the RS 485 cable line For details...
Страница 19: ...ir conditioner to ON Close as much as possible Gr1 Gr5 Gr8 Gr16 Gr32 Gr32 Gr32 Gr112 Gr2 Gr10 Gr17 Gr97 Gr99 Gr22 Gr25 Gr105 Gr107 Gr30 Gr109 Gr32 Gr128 Gr113 Gr114 Gr119 Gr122 Gr124 Gr19 LINK1 terminal Central control wiring Uh line LINK2 terminal Central control wiring Uh line Group 1 to 16 Group 17 to 32 Group 97 to 112 Group 113 to 128 Gr Group Hub LAN cable LAN cable RS 485 Power meter interf...