TOSVERT VF-FS1 series

BACnet

®

option unit

Instruction Manual

NOTICE

1. Make sure that this instruction manual is delivered to the end user of BACnet

®

option

unit.

2. Read this manual before installing or operating the BACnet

®

option unit. Keep it in a

safe place for reference.

3. All information contained in this manual are subject to change without notice. Please

confirm the latest information on our web site

³

www.inverter.co.jp

´

.

Содержание BCN002Z

Страница 1: ...al is delivered to the end user of BACnet option unit 2 Read this manual before installing or operating the BACnet option unit Keep it in a safe place for reference 3 All information contained in this manual are subject to change without notice Please confirm the latest information on our web site www inverter co jp ...

Страница 2: ...o injury 1 to people or that these errors may cause damage to physical property 2 1 Such things as injury burns or shock that will not require hospitalization or long periods of outpatient treatment 2 Physical property damage refers to wide ranging damage to assets and materials Meanings of symbols Marking Meaning of marking Indicates prohibition Do not do it What is prohibited will be described i...

Страница 3: ... electrostatic discharge sensitive device Handle it where the environment is protected against electrostatic electricity Otherwise permanent damage to device will result Transportation and installation Danger Prohibited Do not apply a dropping shock or other physical shocks Otherwise damage or malfunction will result Do not install or operate the inverter if it is damaged or any part of it is miss...

Страница 4: ...unication error trip time Between the inverter and option board f803 Network timeout f892 See the VF FS1 BACnet Communication Function Manual for details Deactivated option unit may cause an accident if the Communication error trip function is not properly set up Make sure that the operation signals are STOP before resetting inverter s fault The motor may suddenly start and that may result in inju...

Страница 5: ...ite www inverter co jp VF FS1 BACnet Communication Function Manual E6581404 After reading this instruction manual please keep it handy for future reference BACnet is a registered trademark of ASHRAE Part numbering BCN 002 Z 0 Revision number Cable length Z means without cable Model number of BACnet option Symbol of BACnet option Accessory check list BACnet communication option is shipped together ...

Страница 6: ...on method 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 8 3 2 Description of terminals 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 9 3 3 Network cable connection 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 10 3 4 Network configuration㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 10 3 5 Wiring of a control terminal 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯...

Страница 7: ... is connected the internal communication line is switched to RS485 then the communication via BACnet network is disabled In this case communication error trip time f803 is also active Use RS485 serial communication option specified by Toshiba Detachable terminal Network communication Communication condition monitor LED Input terminal SINK SOURCE VIB PTC select SW Optional RS485 communication port ...

Страница 8: ...rk condition and connection of the cable C Green LED ON Red LED OFF 0 5s ON 0 5s Invalid configuration detected ADR max master or an option is connected to RJ45 D Green LED Flashing 3 times in 2 seconds Off for 1 second Red LED OFF Waiting for Auto baud rate detection E Green LED Flashing Intermittent Green Red LED Valid message received for this node F Green LED Red LED Flashing Intermittent Red ...

Страница 9: ...ption over the insulating sheet and secure it with the board fixing screw tightening torque of M3 tapping screw 0 7 to 0 8Nm 6 Set up the SW of the board with the input terminal for sink or source 7 Stick the cabling label for BACnet communication option on the standard cabling label stuck on the reverse side of the VF FS1 front cover And stick the BACnet communication option nameplate near the st...

Страница 10: ...rammable analog input with internal pull up resistor for PTC 0 to 10VDC input Using this terminal as PTC input set SW2 to PTC side and set the parameters f645 and f646 to proper value VIB 15k VIB P10 PTC 15k 3 3k CC Control circuit s equipotential terminal P24 24 VDC power supply output 24VDC 50mA P24 P24 PTC FLA FLB FLC Multifunctional programmable relay contact outputs 1c contact 30VDC 0 5A 250V...

Страница 11: ...eption data cables Signal common GND GND is the signal common Grounding the shield of cable SCR Connect the all shield lines of network cable The shield shall be grounded at one end only prevent currents from being created Termination resistor A termination resistance of 120 ohms plus or minus 5 shall be connected at each of the two ends of the segment medium This option has a termination resistor...

Страница 12: ...parate from the power cables to prevent from malfunctioning due to electromagnetic noise N B Provide an inter lock system stated in below when using a programmable controller that has the open collector output When the programmable controller is turned off with the inverter is on the difference between each control power potential will cause wrong signals to the inverter as shown in below figure P...

Страница 13: ...r by disconnection 0 Inverter stop communication command frequency mode open by cmod fmod 1 None continued operation 2 Deceleration stop 3 Coast stop 4 Communication error err5 trip or Network error err8 trip 0 f890 Address Set node address 0 f891 Network baud rate 0 AUTO adaptive 1 9600 2 19 2kbps 3 38 4kbps 4 76 8kbps Over 5 is AUTO adaptive 0 f892 Network Time Out 0 No action Unit 0 1sec Settin...

Страница 14: ... circuits F R Slide switch SW enable to select logical configurations Source Sink Not isolated Logic output terminal Nothing Relay contact output terminal 1 circuit FL 30VDC 0 5A 250VAC 1A cosI 1㧕 250VAC 0 5A cosI 0 4 Isolated Analog input terminals 1 circuit VIB 10VDC RIN 30kohm Not isolated Analog output terminals Nothing Power supply output 24VDC 50mA Current limit function BACnet option networ...

Страница 15: ...r damage the repair cost shall be borne by the customer even within the warranty period i Failure or damage caused by improper or incorrect use or handling or unauthorized repair or modification of the inverter ii Failure or damage caused by the unit falling or an accident during transportation after the purchase iii Failure or damage caused by fire salty water or wind corrosive gas earthquake sto...