66
4400 Series Installation and Operation Manual – 64527-008
11.6
50kVA Specifications – w/ Internal Battery
Backup
Note: The 4400 80kVA unit is not available with internal battery backup.
4400 SPECIFICATIONS: 50kVA w/ Internal Battery Backup
Specification
50kVA
GENERAL
Model Number
B – Internal Batt. Backup
4400F3F500XAB
Capacity Output
50kVA (45kW)
Topology
Double conversion all-IGBT UPS
INPUT
Voltage (V)
208/120 V +10% to -15%
(Intermittently to -30% at 70% load
1
)
3P/4W +GND
Current (Nominal) (A)
140 A
Current (Max) (A)
173 A
Current Limit (%)
125% of Rated load
Current THD (%)
< 5%
Frequency (Hz) [and range]
50/60 Hz ± 5 Hz
Input Power Factor (PF) @ full load
>0.98
Walk-in Function (sec)
20% to 100% over 3, 5, or 9 sec. (Selectable)
Cold Start (0-100% load) (sec)
25 sec. from cold start
BYPASS
Voltage (V)
208/120 V, 3P/4W +GND
Frequency (Hz)
50/60 Hz ±5%
Bypass Overload @ 125% Load
10 min. @ 125% Load
Bypass Overload @ 150% Load
2 min. @ 150% Load
Bypass Overload @ 1000% Load
1 cycle @ 1000% Load
Automatic Retransfer (Max load % for Retansfer)
Yes
OUTPUT
Voltage (V)
208/120 V, 3P/4W +GND
Voltage Regulation (%)
± 2% at 0-100% Balanced Load
Voltage Total Harmonic Distortion (Full Linear Load) (%)
< 3%
Output Voltage Adjustment (%)
± 5% via
Touchscreen
Voltage Transient Response (%) @ 100% Step Load
Change
± 3% @ 100% Step Load Change
Voltage Transient Response (%) @ Loss and Return of
Input V
± 2%
Voltage Transient Response (%) @ Xfer from Bypass to
Inverter
± 3%
Current (A)
139 A
Max Continuous Overload Current (A)
109% of Nominal Output
Crest Factor
2.5
Inrush Current Protection
Fuse
Interrupt Rating (RMS Symmetrical kA)
18 kAIC
1 - Requires adjustment of factory/service adjustable parameters.
Содержание 4400 Series
Страница 2: ......
Страница 6: ...This page left intentionally blank ...
Страница 10: ...This page left intentionally blank ...
Страница 114: ...104 4400 Series Installation and Operation Manual 64527 008 This Page Intentionally Left Blank ...
Страница 117: ...107 4400 Series Installation and Operation Manual 64527 008 FIGURE A 3 4400 50 KVA PHYSICAL DIMENSIONS 1 2 ...
Страница 118: ...108 4400 Series Installation and Operation Manual 64527 008 FIGURE A 4 4400 50 KVA PHYSICAL DIMENSIONS 2 2 ...
Страница 119: ...109 4400 Series Installation and Operation Manual 64527 008 FIGURE A 5 4400 80 KVA PHYSICAL DIMENSIONS ...
Страница 120: ...110 4400 Series Installation and Operation Manual 64527 008 FIGURE A 6 4400 100 KVA PHYSICAL DIMENSIONS ...
Страница 136: ...This page left intentionally blank ...
Страница 137: ......