6.4 UPS Component Information
Component General Name
Life Expectancy (in years)
Standard Operating
Condition*
Maximum Severity Operating
Condition**
Thyristors / SCRs
15
10
Power Magnetic Components (transformers, reactors /
inductors, coils)
15
8
Control Power Supply
15
8
Resistors
15
8
IGBTs
12
8
Contactors
12
8
Control Relays
12
8
Electrolytic Capacitors
10
8
AC Capacitors
10
8
Printed Circuit Boards (PCB)
10
7
LCD
10
7
Fuses
10
7
Thermal Relays
10
7
Cooling Fans
6
5
* Standard Operating Condition is defined as: The UPS installed location where the annual average temperature is be
-
tween 77 °F (25 °C) and 32°F (0° C) with no greater temperature of 89°F (32°C) in a clean environment (ISO 6) with 3 to 4
air changes per hour without any contaminating gases. The UPS load is constant 10 to 90% of UPS rated capacity.
** Maximum Severity Operating Condition is defined as: The UPS installed location where the annual average tempera
-
ture is 104°F (40°C) in an environment above ISO 6 with air changes less than 3 per hour without any contaminating
gases. The UPS load is at or above 100% of UPS rated capacity and may not be constant.
Notes:
Component life expectancy shown is based on the recommended preventative maintenance of once per year on the UPS.
Component Life Expectancy calculations are based on component manufacturer’s recommendations. Previous Toshiba
UPS models similar to the 4400 Series UPS in design and topology (Toshiba 4000, 4100, 4200, and 4200FA Series UPS),
Component Life Expectancy exceed years shown above in both Operating Conditions by over 25%.
Internal VRLA Batteries are not included in the table. Battery life expectancy is dependent on application and the amount
of discharges. Typical VRLA battery life for the Toshiba 4400 Series UPS in standard operating condition with less than 70
battery discharges is 4 to 5 years.
Содержание 4400 Series
Страница 2: ......
Страница 6: ...This page left intentionally blank ...
Страница 10: ...This page left intentionally blank ...
Страница 114: ...104 4400 Series Installation and Operation Manual 64527 008 This Page Intentionally Left Blank ...
Страница 117: ...107 4400 Series Installation and Operation Manual 64527 008 FIGURE A 3 4400 50 KVA PHYSICAL DIMENSIONS 1 2 ...
Страница 118: ...108 4400 Series Installation and Operation Manual 64527 008 FIGURE A 4 4400 50 KVA PHYSICAL DIMENSIONS 2 2 ...
Страница 119: ...109 4400 Series Installation and Operation Manual 64527 008 FIGURE A 5 4400 80 KVA PHYSICAL DIMENSIONS ...
Страница 120: ...110 4400 Series Installation and Operation Manual 64527 008 FIGURE A 6 4400 100 KVA PHYSICAL DIMENSIONS ...
Страница 136: ...This page left intentionally blank ...
Страница 137: ......