4400 Series Installation and Operation Manual – 64527-008
Appendix D – Internal XFMR Unit Input/Output Cabling Guide
The 4400 Series UPS can be configured with a variety of Input and Output voltage transformers to accommodate different Input/Output voltage combinations.
The following tables and text assist with sizing cable for units with non-native input and output voltages.
Table D.1 – UPS Power Lug Cable Capacity and Torque Specifications
Table D.2 –
Recommended Minimum Input Cable Size for 3-Phase/4-Wire + G
Table D.3 –
Recommended Minimum Output/Bypass Cable Size for 3-Phase/4-Wire + G
Table D.4 – Recommended Minimum Cable Size for 3-Phase/3-Wire + G
Table D.5 – Recommended Minimum Cable Size for 3-Phase/3-Wire + G
Table D.6 – Recommended Battery Cabling
Table D.7 – Input Transformer Current for Given Input Voltage
Table D.8 – Output Transformer Current for Given Output Voltage
Tables D.2 and D.3 list the recommended Power Cable sizing for each of the UPS – Vin/Vout transformers. Ampacity should be determined using Table
310.15(B)(16) of the NEC (National Electrical Code) for 75° copper conductors.
NOTES:
•
3-Phase/4-Wire cable sizing calculations based on 4-6 current carrying conductors per conduit.
(NEC Table
310.15(B)(2)(a))
•
Neutral cable sizing in Table D.2 and D.3 is based on allowing, when possible, 1.7 x I(line) for current carrying Neutral.
Otherwise, the maximum cable size allowed by the UPS power lug is specified.
•
80 kVA
–
For ease of installation, consider the alternative of substituting two (2) line-sized neutral cables in place of a
single larger neutral cable in 3-Phase, 4-Wire 80kVA installations
D.1 – UPS Power Lug Cable Capacity and Torque Specifications
TABLE D.1 – UPS POWER LUG CABLE CAPACITY AND TORQUE SPECIFICATIONS
UPS
POWER LUG CABLE CAPACITY
TORQUE
15-30kVA
(1) x #12 to #2
87 in-lb (9.8 N∙m)
50kVA
(1) x #6 to 250 kcmil
275 in-lb (31 N∙m)
80kVA
(2) x 1/0 to 600 kcmil
375 in-lb (42 N∙m)
D.2 – Input Cable Size for 3-Phase/4-Wire + G
TABLE D.2 – RECOMMENDED INPUT CABLE SIZE FOR 3-PHASE/4-WIRE + G
1
Vin, Vout, Vbyp
3P/4W+G
15kVA
(AWG)
20kVA
(AWG)
25kVA
(AWG)
30kVA
(AWG)
50kVA
(AWG)
80kVA
(AWG)
208/120V (no
Xfmr)
Phase
#4
#3
#2
#2
4/0
500 kcmil
Neutral
#2
#2
#2
#2
250 kcmil
2 x 500 kcmil
220/127V
Phase
#4
#3
#2
#2
4/0
500 kcmil
Neutral
#2
#2
#2
#2
250 kcmil
2 x 350 kcmil
230/133V
Phase
#6
#4
#3
#2
3/0
500 kcmil
Neutral
#3
#2
#2
#2
250 kcmil
2 x 300 kcmil
240/139V
Phase
#6
#4
#3
#2
4/0
400 kcmil
Neutral
#2
#2
#2
#2
250 kcmil
2 x 300 kcmil
380/220V
Phase
#8
#6
#6
#4
#1
3/0
Neutral
#4
#3
#2
1/0
4/0
500 kcmil
Содержание 4400 Series
Страница 2: ......
Страница 6: ...This page left intentionally blank ...
Страница 10: ...This page left intentionally blank ...
Страница 114: ...104 4400 Series Installation and Operation Manual 64527 008 This Page Intentionally Left Blank ...
Страница 117: ...107 4400 Series Installation and Operation Manual 64527 008 FIGURE A 3 4400 50 KVA PHYSICAL DIMENSIONS 1 2 ...
Страница 118: ...108 4400 Series Installation and Operation Manual 64527 008 FIGURE A 4 4400 50 KVA PHYSICAL DIMENSIONS 2 2 ...
Страница 119: ...109 4400 Series Installation and Operation Manual 64527 008 FIGURE A 5 4400 80 KVA PHYSICAL DIMENSIONS ...
Страница 120: ...110 4400 Series Installation and Operation Manual 64527 008 FIGURE A 6 4400 100 KVA PHYSICAL DIMENSIONS ...
Страница 136: ...This page left intentionally blank ...
Страница 137: ......