Instruction manual - SAS 16.6 - 1. Installation conditions
300801_en - 12/12
1-9
1.4.4.
Air extraction specifications
1.4.4.1. Minimum room volume
1.4.4.2. Ventilation of premises
Information!
According to DIN 14497, the minimum room volume per machine must be 10m
3
per kilogram of
CO
2
in order to allow use of the fire-fighting equipment (reference 5483).
Warning!
If the room volume is too small, there is a risk of death from asphyxiation when using the fire-
fighting device.
Minimum shop volume per machine
Name
Unit
Value
SAS 16.6
m
3
100
Information!
The premises where the machine is installed must be adequately ventilated.
Mandatory!
Observe the regulations in force in the country of installation.