28
Access level 1:
- Motor starting and stopping:
The sequential start timer set-point, in seconds, will delay an automatic motor starting.
The run period timer, in minutes, will delay the stopping of the motor when the automatic run cause of an automatic
stop configured controller has returned to normal and that no other run causes are present.
Access level 2:
- Transition Timer: Will set the time for which a motor is in the temporary starting wiring configuration. When this
timer expires, the motor will be wired in delta.
Voltage Calibration
Config > Advanced > Voltage
To calibrate the voltage sensing element of a power source, enter the 3 phase voltages as read on a calibrated
meter then press compute. In the case of a transfer switch model, 3 additional voltages need to be calibrated the
same way.
Current Calibration
Config > Advanced > Current
To calibrate a particular current sensing element, enter the current value as read from a calibrated ammeter and
then press COMPUTE. For best results, press the ZERO button when no current is flowing through the sensing
element before calibrating.