GTM1 User manual V-2020-08-12
29 |
E N
In addition:
•
If you use IO3/D0 as inputs for security system sensors
•
You have to set IO3 Settings to 0-30V Analog Input (Zone or
sensor)
•
In SERA2> System Options> General System Options window
•
Press “Write” icon
Go to
-
SERA2> Inputs/ Burglar Alarm Zones window
-
Double click on the selected line
-
Edit default settings
-
Press “Write” in the command line
4.2.12 Fire alarm and Smoke sensors
4.2.12.1 Guidelines for Locating Smoke Detectors and CO Detectors
The following information is for general guidance only and it is recommended that local fire codes and regulations be consulted when locating and installing
smoke and carbon monoxide alarms.
Smoke Detectors. Research indicates that all hostile fires in homes generate smoke to a greater or lesser extent. Detectable quantities of smoke precede
detectable levels of heat in most cases. Smoke alarms should be installed outside of each sleeping area and on each level of the home.
Additional smoke alarms beyond those required for minimum protection be installed. Additional areas that should be protected include: the basement;
bedrooms, especially where smokers sleep; dining rooms; furnace and utility rooms; and any hallways not protected by the required units.
On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air movement,
the presence of joists, uninsulated ceilings, etc.
• Do not locate smoke detectors at the top of peaked or gabled ceilings; dead air space in these locations may prevent smoke detection.
• Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector may prevent smoke from entering the
unit.
• Do not locate detectors in areas of high humidity.
• Do not locate detectors in areas where the temperature rises above 38
o
C (100
o
F) or falls below 5
o
C (41
o
F).
Where required by applicable laws, codes, or standards for a specific type of occupancy, approved single- and multiple-station smoke alarms shall be
installed as follows:
(1)
In all sleeping rooms and guest rooms.
Figure 47 SERA2> Outputs (PGM)
Figure 48 SERA2> Outputs (PGM)
Figure 49 SERA2> Outputs (PGM)
Figure 50 SERA2> System Options> General System Options
Figure 52 SERA2> Inputs/ Burglar Alarm Zones
Figure 51 SERA2> Inputs/ Burglar Alarm Zones