6 – Switches 

BCS10/MCS10

 

Parts Sheet #3600-4011_18_BCS10ps

PERFORMANCE

  THE NOTCHED 

FACE OF THE 

SWITCH INDICATES 

THE SENSING 

SURFACE AND 

MUST FACE 

TOWARD THE 

MAGNET.

  THE NOTCHED 

GROOVE IN THE 

ACTUATOR 

INDICATES THE 

GROOVE TO 

INSTALL THE 

SWITCH. 

CONTACT 

TOLOMATIC IF 

SWITCHES ARE 

REQUIRED ON 

ANOTHER SIDE OF 

ACTUATOR.

0

50

100

150

200

0

100

200

300

400

500

VO

LT

AGE A.C.

 or D

.C.

CURRENT D.C (mA)

REED FORM 

A

R

EE

D FO

RM C

TEMP. vs CURRENT, DC REED

VOLTAGE DERATING, DC REED

TEMP. vs CURRENT, AC REED

0

100

200

300

400

500

600

0

20

40

60

80 100 120 140 160

LO

AD CURRENT (mA)

OPERATING TEMPERATURE ( F)

REED FORM C

 REED FORM A

0

200

400

600

800

1000

0

20 40 60 80 100 120 140 160

LO

AD CURENT (mA)

OPERATING TEMPERATURE ( F)

TRIAC

R T

 & 

R M

 DC REED, FORM A

B T

 & 

B M

 DC REED, FORM C

C T

 & 

C M

 AC REED, TRIAC

T T

 & 

T M

 HALL-EFFECT, SOURCING, PNP

K T

 & 

K M

 HALL-EFFECT, SINKING, NPN

REED

SWITCH

LOAD

BROWN

BLUE

(-)

(-)

(+)

(+)

REED

SWITCH

LOAD

BROWN

BLUE

(-)

(-)

(+)

(+)

OR

AC 

COM 

LOAD

 

INPUT

TRIAC

SWITCH

120Vac

Max.

MOV

BROWN

BLUE

REED

SWITCH

COMMON

NORMALLY CLOSED

NORMALLY OPEN

BROWN

BLACK

BLUE

HALL-EFFECT

SOURCING

SWITCH

BLACK

LOAD

BROWN

BLUE

(-)

(+)

(-)

(+)

HALL-EFFECT

SINKING

SWITCH

BROWN

BLACK

BLUE

(-)

(+)

(-)

(+)

LOAD

WIRING DIAGRAMS

INSTALLATION INFORMATION

Some actuators may 

require switch mount-

ing on a specific side 

of the assembly. Call 

Tolomatic for details.

 Female Connector   5M

SWITCHES

There are 10 sensing choices: DC reed, form A (open) or form C (open or 

closed); AC reed (Triac, open); Hall-effect, sourcing, PNP (open); Hall-effect, 

sinking, NPN (open); each with either flying leads or QD (quick disconnect). 

Commonly used to send analog signals to PLC (programmable logic 

controllers), TLL, CMOS circuit or other controller device. These switches are 

activated by the actuator’s magnet. 
Switches contain reverse polarity protection. QD cables are shielded; shield 

should be terminated at flying lead end. 
If necessary to remove factory installed switches, be sure to reinstall on the 

same of side of actuator with scored face of switch toward internal magnet. 

** 

WARNING

: Do not exceed power rating (Watt = Voltage X Amperage). Permanent damage to sensor will occur.

*QD = Quick Disconnect;  Male coupler is located 6" [152mm} from sensor, 

 

Female coupler to fl ying lead distance is 197" [5m] also see Cable Shielding specifi cation above

REPLACEMENT OF QD SWITCHES MANUFACTURED BEFORE JULY 1, 1997: 

It will be necessary to replace or rewire the female end coupler.

CAUTION: DO NOT OVER TIGHTEN SWITCH HARDWARE WHEN INSTALLING!

CURRENT

Quick disconnect 

Wiring

BROWN

BLACK

BLUE

+

-

SIGNAL

OLD

Quick disconnect 

Wiring

BROWN

BLACK

BLUE

+

-

SIGNAL

Shielded from the female quick disconnect coupler to the fl ying leads. Shield should be terminated at fl ying lead end.

§

 Maximum current 500mA (not to exceed 10VA) Refer to Temperature vs. Current graph and Voltage Derating graph

§§

 Maximum current 250mA (not to exceed 3VA) Refer to Temperature vs. Current graph and Voltage Derating graph

Reed Switch Life Expectancy:

 Up to 

200,000,000 cycles (depending on load cur-

rent, duty cycle and environmental conditions) 

DC REED, AC REED (TRIAC) 

AND HALL-EFFECT 

QUICK-DISCONNECT 

COUPLER  - MALE END

QUICK-DISCONNECT 

COUPLER  - FEMALE END

SPECIFICATIONS

REED DC

REED AC

HALL-EFFECT DC

ORDER CODE

R T

R M

B T

B M

C T

C M

T T

T M

K T

K M

LEAD

5m

QD*

5m

QD*

5m

QD*

5m

QD*

5m

QD*

CABLE SHIELDING

Unshielded

Shielded†

Unshielded

Shielded†

Unshielded

Shielded†

Unshielded

Shielded†

Unshielded

Shielded†

SWITCHING LOGIC

"A" Normally Open

"C" Normally Open or Closed

Triac Normally Open

PNP (Sourcing) Normally 

Open

NPN (Sinking) Normally Open

MECHANICAL CONTACTS

Single-Pole Single-Throw

Single-Pole Double-Throw

Single-Pole Single-Throw

NO, These Are Solid State Components

COIL DIRECT

Yes

Yes

Yes

POWER LED

None

None

None

None

None

SIGNAL LED

Red

Red

Red

OPERATING VOLTAGE

200 Vdc max.

120 Vdc max.

120 Vac max.

5 - 25 Vdc

OUTPUT RATING

25 Vdc, 200mA dc

OPERATING TIME

0.6 msec max. 

(including bounce)

0.7 msec max. 

(including bounce)

< 10 micro sec.

OPERATING TEMPERATURE

-40°F [-40°C] to 158°F [70°C]

0°F [-18°C] to 150°F [66°C]

RELEASE TIME

1.0 msec. max.

ON TRIP POINT

150 Gauss maximum

OFF TRIP POINT

40 Gauss minimum

**POWER RATING (WATTS)

10.0 

§

3.0 

§ §

10.0

5.0

VOLTAGE DROP

2.6 V typical at 100 mA

NA

RESISTANCE

0.1

 Ω

 Initial (Max.)

CURRENT CONSUMPTION

1 Amp at 

86°F [30°C]

0.5 Amp at 

140°F [60°C]

200 mA at 25 Vdc

FREQUENCY

47 - 63 Hz

CABLE MIN. 

BEND 

RADIUS

STATIC

0.630" 

[16mm]

  

DYNAMIC

Not Recommended

SWITCHES

There are 10 sensing choices: DC reed, form A (open) or form C (open or 

closed); AC reed (Triac, open); Hall-effect, sourcing, PNP (open); Hall-effect, 

sinking, NPN (open); each with either flying leads or QD (quick disconnect). 

Commonly used to send analog signals to PLC (programmable logic 

controllers), TLL, CMOS circuit or other controller device. These switches are 

activated by the actuator’s magnet. 
Switches contain reverse polarity protection. QD cables are shielded; shield 

should be terminated at flying lead end. 
If necessary to remove factory installed switches, be sure to reinstall on the 

same of side of actuator with scored face of switch toward internal magnet. 

** 

WARNING

: Do not exceed power rating (Watt = Voltage X Amperage). Permanent damage to sensor will occur.

*QD = Quick Disconnect;  Male coupler is located 6" [152mm} from sensor, 

 

Female coupler to fl ying lead distance is 197" [5m] also see Cable Shielding specifi cation above

REPLACEMENT OF QD SWITCHES MANUFACTURED BEFORE JULY 1, 1997: 

It will be necessary to replace or rewire the female end coupler.

CAUTION: DO NOT OVER TIGHTEN SWITCH HARDWARE WHEN INSTALLING!

CURRENT

Quick disconnect 

Wiring

BROWN

BLACK

BLUE

+

-

SIGNAL

OLD

Quick disconnect 

Wiring

BROWN

BLACK

BLUE

+

-

SIGNAL

Shielded from the female quick disconnect coupler to the fl ying leads. Shield should be terminated at fl ying lead end.

§

 Maximum current 500mA (not to exceed 10VA) Refer to Temperature vs. Current graph and Voltage Derating graph

§§

 Maximum current 250mA (not to exceed 3VA) Refer to Temperature vs. Current graph and Voltage Derating graph

Reed Switch Life Expectancy:

 Up to 

200,000,000 cycles (depending on load cur-

rent, duty cycle and environmental conditions) 

DC REED, AC REED (TRIAC) 

AND HALL-EFFECT 

QUICK-DISCONNECT 

COUPLER  - MALE END

QUICK-DISCONNECT 

COUPLER  - FEMALE END

SPECIFICATIONS

REED DC

REED AC

HALL-EFFECT DC

ORDER CODE

R T

R M

B T

B M

C T

C M

T T

T M

K T

K M

LEAD

5m

QD*

5m

QD*

5m

QD*

5m

QD*

5m

QD*

CABLE SHIELDING

Unshielded

Shielded†

Unshielded

Shielded†

Unshielded

Shielded†

Unshielded

Shielded†

Unshielded

Shielded†

SWITCHING LOGIC

"A" Normally Open

"C" Normally Open or Closed

Triac Normally Open

PNP (Sourcing) Normally 

Open

NPN (Sinking) Normally Open

MECHANICAL CONTACTS

Single-Pole Single-Throw

Single-Pole Double-Throw

Single-Pole Single-Throw

NO, These Are Solid State Components

COIL DIRECT

Yes

Yes

Yes

POWER LED

None

None

None

None

None

SIGNAL LED

Red

Red

Red

OPERATING VOLTAGE

200 Vdc max.

120 Vdc max.

120 Vac max.

5 - 25 Vdc

OUTPUT RATING

25 Vdc, 200mA dc

OPERATING TIME

0.6 msec max. 

(including bounce)

0.7 msec max. 

(including bounce)

< 10 micro sec.

OPERATING TEMPERATURE

-40°F [-40°C] to 158°F [70°C]

0°F [-18°C] to 150°F [66°C]

RELEASE TIME

1.0 msec. max.

ON TRIP POINT

150 Gauss maximum

OFF TRIP POINT

40 Gauss minimum

**POWER RATING (WATTS)

10.0 

§

3.0 

§ §

10.0

5.0

VOLTAGE DROP

2.6 V typical at 100 mA

NA

RESISTANCE

0.1

 Ω

 Initial (Max.)

CURRENT CONSUMPTION

1 Amp at 

86°F [30°C]

0.5 Amp at 

140°F [60°C]

200 mA at 25 Vdc

FREQUENCY

47 - 63 Hz

CABLE MIN. 

BEND 

RADIUS

STATIC

0.630" 

[16mm]

  

DYNAMIC

Not Recommended

REPLACEMENT OF QD SWITCHES 

MANUFACTURED BEFORE JULY 1, 1997:  

It will be necessary  

to replace or  

rewire the  

female end  

coupler.

3. SWITCHES

 NOTE:

 Form A Reed Switches should not be used in TTL logic cir-

cuits. A voltage drop caused by the L.E.D. indicator will result.For 

applications where TTL circuits are used, please contact the factory.

 WARNING

: An ohmmeter is recommended for testing Reed 

Switches. NEVER use an incandescent light bulb as a high current 

rush may damage the switch.

 

Reed and TRIAC switches are only recommended for signalling 

position, not directly powering solenoids. For shifting a solenoid, a 

relay or resistor is recommended between it and the Reed Switch. 

Switch ratings must not be exceeded at any time.

 

NOTE:

 For Hall Effect Switch Magnet, be sure the S pole of the mag-

net (indicated with black dot) is facing toward the switch (down).

Switch Ordering NOTES:

To order field retrofit switch and hardware kits for all Tolomatic actuators: 

SW (Then the model and bore size, and type of switch required)

Example: SWBCS10RT 

(Hardware and Form A Reed switch with 5 meter lead for 1" size 

BCS actuator)

Mounting hardware is required if replacing switch for any actuator 

manufactured before 7/1/97

SWITCH KIT

34.

CONFIG. CODE ORDERING

Mounting Hardware & FE conn. included

CODE

 DESCRIPTION

BT

 Switch Only, Reed, Form C, 5m

BM

 Switch Only, Reed, Form C, Male Conn.

RT

 Switch Only, Reed, Form A, 5m

RM

 Switch Only, Reed, Form A, Male Conn.

CT

 Switch Only, Triac, 5m

CM

 Switch Only, Triac, Male Conn.

KT

 Switch Only, Hall-effect, Sinking, 5m

KM

 Switch Only, Hall-effect, Sinking, Male Conn.

TT

 Switch Only, Hall-effect, Sourcing, 5m

TM

 Switch Only, Hall-effect, Sourcing, Male Conn.

NOTE: When ordered by Config. Code Female connector & all mounting hardware 
is included