Page    01                                                                                           KKAI808PE01-A/0-20130904

AI808P

AI808P Series Intelligent Temperature Controller User Manual

Features:

 TC / RTD / Analog signal universal input;

 With display, alarm, adjusting and communication function;

 Advanced Fuzzy algorithm & Two Degrees 

      of Freedom PID Arithmetic;

 Optional control output, modularization design;

 Good anti-interference;

 Up to 50 programmable segments control;

 Color bar display

AI808 Series Intelligent Temperature Controller (with 50 programmable segment control)

1. Model

Safe Caution

  Please comply with the below important points.

Warning
Notice

 An accident may happen if the operation does not comply with the instruction.

 An operation that does not comply with the instruction may lead to product damage.

For your safty, please read following content carefully before you are using our temperature controller!

The instruction of the symbol in the manual is as below.

An accident danger may happen in a special condition.

Please read the manual carefully before you use the temperature controller.

Warning

1. A safty protection equipment must be installed or please contact with us for the relative information if the product is used under 

    the circumstance such as nuclear control, medical treatment equipment, automobile, train, airplane, aviation and equipment etc..

    Otherwise, it may cause serious loss, fire or person injury.

2. A panel must be installed, otherwise it may cause creepage (leakage).

3. Do not touch wire connectors when the power is on, otherwise you may get an electric shock.

4. Do not dismantle or modify the product. If you have to do so, please contact with us first. Otherwise it may cause electric shock

    and fire.

5. Please check the connection number while you connect the power supply wire or input signal, otherwise it may cause fire. 

Caution

1. This product cannot be used outdoors. Otherwise the working life of the product will become shorter, or an electric shock accident

     may happen.

2. When you connect wire to the power input connectors or signal input connectors, the moment of the No.20 AWG (0.50 mm2) 

     screw tweaked to the connector is 0.74n.m - 0.9n.m.  Otherwise the connectors may be damaged or get fire.

3. Please comply with the rated specification. Otherwise it may cause electric shock or fire, and damage the product.

4. Do not use water or oil base cleaner to clean the product. Otherwise it may cause electric shock or fire and damage the product.

5. This product should be avoid working under the circumstance that is flammable, explosive, moist, under sunshine, heat radiation

     and vibration. Otherwise it may cause explosion.

6. In this unit it must not have dust or deposit, otherwise it may cause fire or mechanical malfunction.

7. Do not use gasoline, chemical solvent to clean the cover of the product because such solvent can damage it. Please use some soft

    cloth with water or alcohol to clean the plastic cover.

Dimension: 4: 48Wx48H   6: 48Wx96H   7: 72Wx72H   8: 96Wx48H   9: 96Wx96H

                   16 80W×160H    80 160W×80H

Output function: R: Relay    S: Logic (SSR)   D: Current (4-20mA)

Alarm function: B: One  Alarm Output     C: Two Alarm Output 

(One more alarm will be added when the heating & cooling control is not used) 

Signal input: 10: One signal input without communication

                      18: One signal input with RS485 communication (please indicate when order)

Содержание AI808P Series

Страница 1: ...e or modify the product If you have to do so please contact with us first Otherwise it may cause electric shock and fire 5 Please check the connection number while you connect the power supply wire or...

Страница 2: ...ly to relay output power supply to signal input relay output to signal input 2000VDC Between the low voltage signal isolated with each other 600VDC 3 Main Technical Parameters Dielectric strength AI80...

Страница 3: ...ight AL2 AL2 Indicating Light SET Function Key OUT1 OUT1 Indicating Light Shift Function Key No 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Increase Key Decrease Key AL3 AL3 Indicating Light AT Auto turn...

Страница 4: ...rol setting method 1 There are total 50 programmable segments For each segment there are 2 settable parameters SV ST 2 SV value is the object control value of a segment for example if SV 01 is 200 the...

Страница 5: ...LD three status in this segment Example Here is a control process with below requirement the relevant setting is on the right side 1 Temperature raise to 300 SV01 300 ST01 0 2 Temperature raise from 3...

Страница 6: ...m PV AL Cancel PV AL HY Alarm PV AL Cancel PV AL HY Alarm PV AL SV Cancel PV SV AL HY Alarm PV SV AL Cancel PV SV AL HY Absolute upper limit alarm Absolute Lower limit alarm Upper Limit deviation alar...

Страница 7: ...e host computer read the float number AL1 The value of Alarm 1 is 15 4 The address code of AL1 is 0x0000 for AL1 is float number 4bits it will occupy 2 data register Reference IEEE 574 standard the he...

Страница 8: ...ss Lo 0x10 6 1 x 0 2 0 x 0 0 0 x 0 0x04 0xFD Data 1 Hi Data 1 Lo Data 2 Hi Data 2 Lo CRC Hi CRC Hi 0x00 0x00 0x44 0x00 0x00 0xFC Correct answer from slave unit Read Multiple Registers 1 2 3 4 5 6 7 8...

Страница 9: ...ection setting value SV3 The 3 section status setting value ST3 The 4 section setting value SV4 The 4 section status setting value ST4 The 5 section setting value SV5 The 5 section status setting valu...

Страница 10: ...section setting value SV21 The 22 section setting value SV22 The 23 section setting value SV23 The 24 section setting value SV24 The 25 section setting value SV25 The 26 section setting value SV26 The...

Страница 11: ...tting value SV45 The 46 section status setting value ST46 The 46 section setting value SV46 The 47 section status setting value ST47 The 47section setting value SV47 The 48 section status setting valu...

Страница 12: ...20130904 unsigned int Get_CRC uchar pBuf uchar num unsigned i j unsigned int wCrc 0xFFFF for i 0 i num i wCrc unsigned int pBuf i for j 0 j 8 j if wCrc 1 wCrc 1 wCrc 0xA001 else wCrc 1 return wCrc 16...

Отзывы: