TOELLNER TOE 9260 Series Скачать руководство пользователя страница 6

 

 

 

TOELLNER Electronic Instrumente GmbH

6

2.2 

E-10, Short interruptions 

 reference measurements 

This section applies to LV 124, version 2013 only. That standard requires reference 
measurements before an interruption test is carried out with the DUT. Such a reference 
measurement gives proof of the slew rate of the switching operation. For the reference 
measurements of the E-10 test the DUT is replaced by a reference resistor of 1 

 ± 5 % 

resp. 100 

 ± 5 % of low parasitic inductance (  Fig. 1). 

To avoid the addition of cable inductivity, the reference resistor shall be connected as close 
to the output sockets of the TOE 9260 as possible. The reference resistors of the 
TOE 9260/100 kit may be connected directly to the output sockets without use of cables. 

Because of the high power loss in case of the 1 

 resistor operated at 11 V according to the 

LV 124, the test setup should be prepared in the powerless state. Test execution should be 
kept as short as possible. 

 

 

2.3 

LV 124, Test E-13, Pin interruption 

The test E-13 has to be applied to signal pins as well as to ground pins. For both situations, 
the test assemblies are explained in the following. 
 

2.3.1 

E-13, interruption of signal pins 

For the interruption of a signal pin, a signal line switch of the TOE 9260 is used. Such a 
signal line switch is applicable for a pin current up to 1 A. 

If up to 2 A have to be switched, two signal line switches can be paralleled. It is not 
recommended to operate more than two switches in parallel. With three or four switches in 
parallel the timing requirements of the LV 124-2013 cannot be fulfilled with a 1 k

 reference 

resistor. (For applications different from the LV 124 / LV 148 standards, there are four signal 
line switches available in the TOE 9260; if e.g. differential pairs or a 4-pole connection shall 
be switched at once.) 

Fig. 2 shows the test assembly with use of one of the signal line switches of the TOE 9260. 
Only one pin has to be interrupted at one time. The test is then sequentially carried out for 
every signal pin of the DUT. 

 

Fig. 2: 

Test assembly for LV 124, E-13; interruption of a signal pin 

Содержание TOE 9260 Series

Страница 1: ...al Line Interruptions for Automotive Tests Electronic Switch TOE 9260 9260E AN001_Rev00 doc R TOELLNER ELECTRONIC INSTRUMENTE GMBH Gahlenfeldstrasse 31 58313 Herdecke Germany 49 0 23 30 97 91 91 Fax 4...

Страница 2: ...E 10 Short interruptions reference measurements 6 2 3 LV 124 Test E 13 Pin interruption 6 2 3 1 E 13 interruption of signal pins 6 2 3 2 E 13 interruption of signal pins reference measurements 7 2 3 3...

Страница 3: ...ice of the right switch i e power switch resp signal line switch of the TOE 9260 Reference measurements according to the requirements of the LV 124 2013 1 1 Required test equipment Commonly the follow...

Страница 4: ...ence resistors 1 100 and 1 k of low inductance 5 tolerance to perform reference measurements The use of the following reference resistor kits is recommended Item No Item name TOE 9260 100 Reference Re...

Страница 5: ...een the power supply and the IN sockets of the TOE 9260 the internal capacitor at the input of the TOE 9260 should be activated by setting the DIP switch INPUT C to ON So the shortest possible rise an...

Страница 6: ...possible 2 3 LV 124 Test E 13 Pin interruption The test E 13 has to be applied to signal pins as well as to ground pins For both situations the test assemblies are explained in the following 2 3 1 E 1...

Страница 7: ...istor TOE 9260 104 may be connected to power source and signal line switch by provided suitable cables Due to the 1 A current limit of a signal line switch the measurement with the 1 resistor shall be...

Страница 8: ...nce resistor of 1 5 resp 1 k 5 of low parasitic inductance To avoid the addition of too high cable inductivity the reference resistor shall be connected close to the signal line switch by closely spac...

Страница 9: ...resistor at a voltage level of 1 V If the DUT is tested with two paralleled signal line switches 2 3 3 the reference measurements have to be carried out with the same configuration of paralleled switc...

Страница 10: ...ould be activated by setting the DIP switch INPUT C to ON So the shortest possible rise and fall times of the voltage at the DUT are achieved If an artificial network between the power supply and the...

Отзывы: