12
AC IN
3P inlet
–
Supplied cable
–
120 V AC, 60 Hz
–
–
DS-SF LINK RJ45 (female)
RJ45 (male)
Cat. 5 STP
RJ45 (male)
VM-3240VA
VM-3240E
DS-SF LINK RJ45 (female)
BATTERY
POWER IN
Screw terminal
Unprocessed cable
end
AWG 6 – AWG 0
(AWG 1/0)
16 – 50 mm
2
(line resistance
within 4 m
Ω
/total)
Unprocessed cable
end
Lead-acid battery
Electrode
(+, –)
–
PS IN
Screw terminal
Round terminal
AWG 10 – AWG 8
5.5 – 8.0 mm
2
(line resistance
within 10 m
Ω
)
Round terminal
VM-3240VA
VM-3240E
PS OUT
Screw terminal
DC POWER
OUT
Screw terminal
Round terminal
Terminal
Name
Equipment
Receptacle
Plug
Cable Type
Plug
Equipment
Terminal
Name
Equipment
Receptacle
Terminal to Connect
Cable Type
Equipment to be Connected to
6. CONNECTION CABLE LIST
Round terminal
VM-3240VA
VM-3240E
DC POWER
IN
2P screw terminal
AWG 10 – AWG 8
5.5 – 8.0 mm
2
Connect cables to 2 PS IN (+) terminals.
Connect 2 cables to PS OUT (+) terminal.
Below is an example showing that one VX-2000DS is used in a system including 3 VM amplifiers.
VM-3240VA
VM-3240E
VM-3240E
Lead-acid Battery*
VX-2000DS
VM LINK
DC POWER
DS LINK
VM LINK
Battery capacity
Min. : 100 Ah
Max. : 100 Ah
*
Number of VX-2000DS units
1
2
3
4
Number of VM amplifiers
1
2
3
4
5
6
7
8
9
10
Min. [Ah]
28
65
100
28
65
100
28
65
100
28
Max. [Ah]
100
100
100
100
100
100
100
100
100
100
[Required number of VX-2000DS units]
The required number of the VX-2000DS Emergency Power Supply units is determined depending on the
application of the system configured with the VM-3240VA and/or VM-3240E (hereinafter called "VM
amplifier").
One VX-2000DS is required every 3 VM amplifiers.
Battery capacity