background image

5

Model No.

PC-1860EN

PC-2360EN

Standards

Certified to the European Standard

EN 54-24: 2008

Loudspeaker for voice alarm systems for fire detection and fire alarm 

systems

Rated Input

6 W (100 V line), 3 W (70 V line)

Rated Impedance

100 V line:  1.7 kΩ (6 W), 3.3 kΩ (3 W), 6.7 kΩ (1.5 W), 13 kΩ (0.8 W)

70 V line:  1.7 kΩ (3 W), 3.3 kΩ (1.5 W), 6.7 kΩ (0.8 W), 13 kΩ (0.4 W)

Sensitivity

94 dB (1 W, 1 m) (500 Hz – 5 kHz, pink noise)

92 dB (1 W, 1 m) (100 Hz – 10 kHz, pink noise)

80 dB (1 W, 4 m) (100 Hz – 10 kHz, pink noise)

Maximum 

Sound Pressure Level

99 dB (6 W, 1 m) (100 Hz – 10 kHz, pink noise)

87 dB (6 W, 4 m) (100 Hz – 10 kHz, pink noise)

Frequency Response

80 Hz – 20 kHz (peak –20 dB)

60 Hz – 20 kHz (peak –20 dB)

Coverage Angle 

(–6 dB)

Horizontal and Vertical:

165° (500 Hz), 175° (1 kHz), 165° (2 kHz),

70° (4 kHz) according to EN 54-24

Horizontal and Vertical:

160° (500 Hz), 170° (1 kHz), 160° (2 kHz),

60° (4 kHz) according to EN 54-24

Environmental type

A (indoor applications)

Speaker Component

12 cm (5") cone-type

16 cm (6") cone-type

Operating Temperature

–10 to +50 °C (14 to 122 °F)

Dimensions for Fixing 

Hole

Mounting hole: 

ø150 ±3 mm

 

(ø5.91" ±0.12")

Ceiling thickness:  5 – 25 mm

 

(0.2" – 0.98")

Mounting hole: 

ø200 ±3 mm

 

(ø7.87" ±0.12")

Ceiling thickness:  5 – 25 mm

 

(0.2" – 0.98")

Speaker Mounting 

Method

Spring clamp

Applicable Cable

Solid wire: 0.5 – 3 mm² (AWG 20 – 12)

Connection

Push wire connection (Bridging terminal-2 branch type)

Finish

Frame: Steel plate, white (RAL 9016 equivalent), paint

Grille:  Steel net, white (RAL 9016 equivalent), paint

Dimensions

ø180 x 70 (d) mm (ø7.09" x 2.76")

ø230 x 76 (d) mm (ø9.06" x 2.99")

Weight

560 g (1.23 lb)

740 g (1.63 lb)

6. SPECIFICATIONS

Notes

•  The design and specifications are subject to change without notice for improvement. 

•  The Specifications data was measured in an anechoic chamber, according to EN 54-24.

•  Reference axis: 

Axis is on the center of grill surface and perpendicular to the grill surface.

•  Reference plane:  Plane is on the grill surface and perpendicular to the reference axis.

•  Horizontal plane:  Plane is containing the reference axis and perpendicular to the reference plane.

• 

Other technical data:  See the specification sheet PC-1860EN/PC-2360EN.

1438

• Accessories
[PC-1860EN] 

Paper pattern  ......................  1

Zip tie  ..................................  2

[PC-2360EN]

Paper pattern  ......................  1

Zip tie  ..................................  3

Содержание PC-1860EN

Страница 1: ...l damage and possible personal injury Ensure that all screws are securely tightened If they are loose after installation the speaker could fall down possibly resulting in personal injury Thank you for purchasing TOA s Ceiling Mount Speaker Please carefully follow the instructions in this manual to ensure long trouble free use of your equipment CEILING MOUNT SPEAKER INSTRUCTION MANUAL PC 1860EN PC ...

Страница 2: ...ic shocks be sure to switch off the amplifier s power when connecting speakers When the Unit is in Use Do not operate the speaker for an extended period of time with the sound distorting Doing so may cause the speaker to heat resulting in a fire Do not stand or sit on nor hang down from the speaker as this may cause it to fall down or drop resulting in personal injury and or property damage Have t...

Страница 3: ...lead in cables cables from the amplifier and lead out cables cables to other speakers into the input connector When making a bridge connection Input connector Matching transformer Speaker cable From the amplifier Speaker cable To the next speaker Input connector From the amplifier To the next speaker COM HOT 9 mm 0 35 Applicable cable Solid wire ø0 8 ø1 6 mm equivalent to AWG 20 14 View with splas...

Страница 4: ...into the mounting hole 4 WIRING DIAGRAMS 8 Ω 13 kΩ 6 7 kΩ 3 3 kΩ 1 7 kΩ Factory preset 0 COM white COM HOT black HOT Matching transformer Input connector COM 5 FREQUENCY RESPONSE 1 W 4 M 5 1 PC 1860EN 5 2 PC 2360EN 60 70 80 90 20 100 1 k 10 k 20 k 50 500 5 k Hz dB 70 80 90 20 100 1 k 10 k 20 k 50 500 5 k dB Hz 60 Speaker cable From the amplifier Splash proof cover Speaker cable To the next speaker...

Страница 5: ...0 C 14 to 122 F Dimensions for Fixing Hole Mounting hole ø150 3 mm ø5 91 0 12 Ceiling thickness 5 25 mm 0 2 0 98 Mounting hole ø200 3 mm ø7 87 0 12 Ceiling thickness 5 25 mm 0 2 0 98 Speaker Mounting Method Spring clamp Applicable Cable Solid wire 0 5 3 mm AWG 20 12 Connection Push wire connection Bridging terminal 2 branch type Finish Frame Steel plate white RAL 9016 equivalent paint Grille Steel...

Страница 6: ......

Страница 7: ......

Страница 8: ...URL https www toa jp 133 01 00250 00 ...

Отзывы: