background image

 

172-65176MA-03  (UFO3 Series)  27  Aug 2015

 

7

 

Installation 

 

 

Install properly and DO NOT use this product outside the recommended 

operating pressure, temperature and other specification ranges. 

Improper use may result in such hazards as damage to the product or 

malfunctions which may lead to serious accidents. Local regulations 

may restrict the use of this product to below the conditions quoted.

 

CAUTION 

 

 

Take measures to prevent people from coming into direct contact with 

product outlets. Failure to do so may result in burns or other injury from 

the discharge of fluids.

 

CAUTION 

 

 

Do not use excessive force when connecting threaded pipes to the 

product. Over-tightening may cause breakage leading to fluid 

discharge, which may cause burns or other injury.

 

CAUTION 

 

Installation, inspection, maintenance, repairs, disassembly, adjustment and valve 
opening/closing should be carried out only by trained maintenance personnel. 

1.  Before installation, be sure to remove all protective seals. 

2.  Before installing the product, open the inlet valve and blow out the piping to 

remove any piping scraps, dirt and oil. Close the inlet valve after blowdown. 

3.  Install the product so the arrow on the body is pointing in the direction of flow. 

4.  The trap should be inclined no more than 5° horizontally and front-to-back. 

5.  Install a condensate outlet valve and outlet piping. 

6.  Open the inlet and outlet valves and check to make sure that the product functions 

properly. 

If there is a problem, determine the cause using the “Troubleshooting” section in this 
manual. 

Tolerance Angle for Installation - 5° 

 

Make sure the trap is installed with the raised 

  lettering on the body horizontal.

 

 

Содержание UFO3-BN

Страница 1: ...03 UFO3 Series 27 August 2015 Free Ball Bucket Steam Trap UFO3 BN UFO3F BN Copyright 2015 by TLV CO LTD All rights reserved ISO 9001 ISO 14001 Manufacturer Kakogawa Japan is approved by LRQA LTD to IS...

Страница 2: ...is out of the ordinary Also be sure to read this manual carefully before use and follow the instructions to be sure of using the product properly The Free Ball Bucket Steam Trap is suitable for appli...

Страница 3: ...ation which poses a threat of death or serious injury WARNING Indicates that there is a potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment...

Страница 4: ...fluids Do not use excessive force when connecting threaded pipes to the product Over tightening may cause breakage leading to fluid discharge which may cause burns or other injury Use only under condi...

Страница 5: ...to back pressure has a check valve TLV CK been installed 5 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 6 Ha...

Страница 6: ...reventing it from closing against the drain jet allowing the discharge of all initial air and cold condensate 2 Entry of Steam When steam flows in the higher temperature causes the bimetal to expand r...

Страница 7: ...ION Refer to the product nameplate for detailed specifications Model Maximum Allowable Temperature TMA Maximum Allowable Pressure Maximum Operating Temperature Nominal Diameter Maximum Differential Pr...

Страница 8: ...use burns or other injury CAUTION Installation inspection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel 1 Before inst...

Страница 9: ...e to steam leakage Normal Condensate together with flash steam is discharged intermittently and the sound of flow can be heard at the time of discharge Blocked Discharge Impossible No condensate is di...

Страница 10: ...re no pieces of the old gasket left on the seating surfaces make sure the arrow points in the direction of condensate flow Cover Gasket Remove being careful not to damage the seating surface and clean...

Страница 11: ...1 N m 10 kg cm NOTE Coat all threaded portions and orifice gasket with anti seize If drawings or other special documentation were supplied for the product any torque given there takes precedence over...

Страница 12: ...ns Steam locking has occurred Perform a bypass blowdown or close the trap inlet piping and allow the trap to cool Steam is discharged or leaks from the outlet blowing steam leakage Build up of rust or...

Страница 13: ...proper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or...

Страница 14: ...ection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel Attaching the Insulation Cover to the Steam Trap 1 Allow the tra...

Отзывы: