Troubleshooting
As glass parts will wear and deteriorate in quality, they should be
replaced annually. Be careful not to damage the glass by striking it with
objects or inflicting any other shocks. If the glass becomes damaged,
subsequent fluid discharge could result in injury or other damage.
WARNING
When disassembling or removing the product, wait until the internal
pressure equals atmospheric pressure and the surface of the product
has cooled to room temperature. Disassembling or removing the
product when it is hot or under pressure may lead to discharge of fluids,
causing burns, other injuries or damage.
CAUTION
When the product fails to operate properly, use the following table to locate the cause
and remedy.
Problem
Cause
Remedy
Ball is not visible
(Glass is dirty)
The glass is dirty
Clean the glass
The guard plate is dirty
Clean the guard plate
There is an build-up of dirt
inside the body
Clean
Leaks to the outside of
the product
Deterioration or damage to
gaskets
Replace with new gaskets
Improper glass holder
tightening torque was used
Tighten to the proper torque
The glass displays wear, cracks
or other damage
Replace with a new glass
The guard plate displays wear,
cracks or other damage
Replace with a new guard plate
Sight glass is damaged
The operating pressure or
temperature exceed the
maximum specified operating
conditions
Compare specifications and
actual operating conditions
The glass has outlived its
projected service life
Replace with a new glass
Ball does not move*
(T8N/TF8N/T8NL/TF8NL)
The body is clogged with dirt, of
there is a build-up on the ball
Clean parts
* For the T10N/TF10N/T10NL/TF10NL, when the condensate load is low, the ball does not move
NOTE: When replacing parts with new, use the parts list for reference, and replace with parts
from the repair kit. Please note that replacement parts are only available as part of the
repair kit.