background image

 

7

Installation 

 

 

Install properly and DO NOT use  this product outside the recommended 

operating pressure, temperature and other specification ranges. 
Improper use may result in such hazards as damage to the product or 

malfunctions which may lead to serious accidents. Local regulations 

may restrict the use of this product to below the conditions quoted.

 

CAUTION

 

 

Take measures to prevent people from coming into direct contact with 

product outlets. Failure to do so may result in burns or other injury from 

the discharge of fluids.

CAUTION

 

Installation, inspection, maintenance, repairs, disassembly, adjustment and valve 
opening/closing should be carried out only by trained maintenance personnel. 

 

1.  Before installation, be sure to remove all protective seals. 
2.  Before installing the product, blow out the inlet piping to remove any piping scraps, 

dirt and oil. Close the inlet valve after blowdown. 

3.  Install the product so that the arrow on the body is pointing in the direction of flow. 
4.  The trap should be inclined no more than 5° in any plane. 
5.  Install a condensate outlet valve and outlet piping. 
6.  Open the inlet and outlet valves and check to make sure that the product functions 

properly. 

If there is a problem, determine the cause using the “Troubleshooting” section in this manual. 

 

Tolerance Angle for Installation - 5° 

(SS3N / SS5N / SS5NH)

 

Tolerance Angle for Installation - 5° 

(SS3V / SS5V / SS5VH)

 

 

 

Install on a horizontal pipe with the nameplate 

facing upwards and the arrow pointing in the 

direction of flow 

Install on a verticle pipe with the inlet on top, 

the outlet on the bottom and the arrow 

pointing in the direction of flow 

 

NOTE: For products with socket weld connections the insulation cover shipped with the 

product should be attached after the products is welded onto the pipe and after its 
surface has cooled to room temperature. 
For attaching the insulation cover, see the instruction below. 

<How to attach the insulation cover> 

Short tape

Long tape

Step 1. Wrap the included sealing tape around the inlet and outlet 

connection at each end of the trap (3 turns for each). 

Step 2. Fit the two halfshells of the insulation cover around the trap 

until the 5 tabs and 5 holes are perfectly aligned. 
A nameplate is affixed to the insulation cover. Make sure 
that direction of the arrow on the nameplate matches the 
direction of condensate flow. 

Step 3. Using the included aluminum tape, seal the area where the 

halfshells meet. Then wrap 3 more turns of sealing tape over 
the top of the sealing tape applied in step 1. 

172-65119MAJ-03 (SS3/SS5)  25 Feb 2014

 

Содержание SS3N

Страница 1: ... SS3 SS5 25 February 2014 ISO 9001 ISO 14001 Manufacturer Kakogawa Japan is approved by LRQA LTD to ISO 9001 14001 Free Float Steam Trap SS3N SS3V SS5N SS5V SS5NH SS5VH Copyright 2014 by TLV CO LTD All rights reserved ...

Страница 2: ... float steam trap uses a precision polished float and three point support for the valve body With no hinges or levers the trap automatically continuously discharges condensate preventing it from collecting The three point seating for the valve body supports the precision polished float securely at three points and ensures a high degree of sealing for even minute quantities of condensate If detaile...

Страница 3: ...or serious injury WARNING Indicates that there is a potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment product damage CAUTION Install properly and DO NOT use this product outside the recommended operating pressure temperature and other specification ranges Improper use may result in such hazards as damage to the product or malfunctions ...

Страница 4: ...ry due to malfunction or the discharge of fluids CAUTION Use only under conditions in which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other injury Use only under conditions in which no water hammer will occur The impact of water hammer may damage the product leading to fluid discharge which may cause burns or other injury 172 65119M...

Страница 5: ...has a check valve TLV CK been installed 5 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 6 Has the piping work been done correctly as shown in the figures below Requirement Correct Incorrect Install catchpot with the proper diameter Diameter is too small Make sure the flow of condensate is not obstructed Diame...

Страница 6: ...ischarge of initial air and cold condensate the heat of the inflowing steam and condensate cause the bimetal air vent strip to contract 2 Condensate Discharge As steam is supplied condensate flow begins The rising condensate level causes the float to rise due to buoyancy opening the orifice and allowing condensate to be discharged 3 Closed Position When the condensate flow rate decreases the float...

Страница 7: ...ns SS3N SS5N SS5NH SS3V SS5V SS5VH Valve No Serial Number Model Nominal Diameter Maximum Allowable Pressure Maximum Operating Temperature Maximum Allowable Temperature TMA Maximum Differential Pressure Maximum Allowable Pressure Maximum Operating Temperature Maximum Allowable Temperature TMA Valve No Serial Number Maximum Differential Pressure Maximum allowable pressure PMA and maximum allowable t...

Страница 8: ... functions properly If there is a problem determine the cause using the Troubleshooting section in this manual Tolerance Angle for Installation 5 SS3N SS5N SS5NH Tolerance Angle for Installation 5 SS3V SS5V SS5VH Install on a horizontal pipe with the nameplate facing upwards and the arrow pointing in the direction of flow Install on a verticle pipe with the inlet on top the outlet on the bottom an...

Страница 9: ...may cause damage to piping and equipment resulting in faulty or low quality products or losses due to steam leakage Normal Condensate is discharged continuously together with flash steam and the sound of flow can be heard If there is very little condensate there is almost no sound of flow Blocked Discharge Impossible No condensate is discharged The trap is quiet and makes no noise and the surface ...

Страница 10: ...ping is clogged with rust and scale Clean the piping The capacity of the trap is insufficient Compare specifications and actual operating conditions No condensate is discharged blocked or discharge is poor Steam locking has occurred Perform a bypass blowdown or close the trap inlet valve and allow the trap to cool Improper installation orientation Correct the installation Steam is discharged or le...

Страница 11: ...by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to disasters or forces of nature 5 Accidents or malfunctions due to any other cause beyond the control of TLV CO LTD 4 U...

Страница 12: ...pen the cover along the Velcro strip 3 Place cover evenly around the body with the arrow on the cover facing the same direction as the arrow on the trap body 4 Reattach the Velcro strip 5 Secure the ends of the cover around the trap inlet and outlet with the binding strips 15 5 8 250 10 100 4 φ50 2 100 4 100 4 200 8 150 6 70 23 4 220 811 16 6 1 4 Insulation Cover Velcro Strip Binding Strip 2pc t 0...

Отзывы: