172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
40
3.3 Parameter Select Mode [B]
Up to 16 screens registered on the Parameter select setting screen (Set data lock
mode) by the user can be displayed.
3.4 Operation Transfer Mode [C]
No.
Symbol
Name
Data range
Factory set
value
User set
value
15
R/S
RUN/STOP transfer
rUn
: RUN (Control start)
SToP
: STOP (Control stop)
STOP
16
1. ATU
Input 1_Autotuning
(AT)
1)
oFF
: PID control
on
: Start Autotuning
When the Autotuning (AT) is finished, the
control will automatically return to “
oFF
.”
oFF
17
2. ATU
Input 2_Autotuning
(AT)
2)
oFF
: PID control
on
: Start Autotuning
When the Autotuning (AT) is finished, the
control will automatically return to “
oFF
.”
oFF
18
1. STU
Input 1_Startup tuning
(ST)
1)
oFF
: ST unused
on1
: Execute once *
on2
: Execute always
* When the ST is finished, the control will
automatically return to “
oFF
.”
oFF
19
2. STU
Input 2_Startup tuning
(ST)
2)
oFF
: ST unused
on1
: Execute once *
on2
: Execute always
* When the ST is finished, the control will
automatically return to “
oFF
.”
oFF
20
1. A/M
Input 1_Auto/Manual
transfer
AUTo
: Auto mode
MAn
: Manual mode
MAN
21
2. A/M
Input 2_Auto/Manual
transfer
3)
AUTo
: Auto mode
MAn
: Manual mode
MAN
22
R/L
Remote/Local transfer
4)
When “Remote setting input” is selected at
Select function for Input 2
5)
LoC
: Local mode
rEM
: Remote mode
LoC
When
“Cascade control” is selected at Select
function for input 2
6)
SnGL
: Single control
CAS
: Cascade control
SnGL
When “Control with PV select” is selected at
Select function for input 2
7)
InP1
: Input 1
InP2
: Input 2
InP1
When “2-loop control/Differential
temperature control” is selected at Select
function for input 2
8)
2LooP
: 2-loop control
dIFF
: Differential temperature control
2LooP
23
L/E
Control area Local/
External transfer
9)
LoC
: Local mode
EXT
: External mode
LoC
1)
Not displayed when "Pressure control operation [MC-(V)COS(R)]" is selected in "Input 1_Control action".
2)
Displayed when "2-loop control/Differential temperature control" is selected in "Select function for Input 2" AND "Pressure control
operation [MC-(V)COS(R)]" is not selected in "Input 2_Control action".
3)
Displayed when one of "Remote setting input", "Cascade control", "Control with PV select", or "2-loop control/Differential
temperature control" is selected, AND in the case of "2-loop control", "PID control" or "Heating/Cooling PID control" is selected in
both Input 1_Control action and Input 2_Control action.
4)
Displayed when "Remote setting input" is selected in "Select function for Input 2."
5)
Displayed when "Cascade control" is selected in "Select function for Input 2."
6)
Displayed when "Control with PV select" is selected in "Select function for Input 2." When "Switching by level" is selected at
"Selection of PV select trigger," the parameter becomes display only.
7)
Displayed when "Control with PV select" is selected in "Select function for Input 2." When "Switching by level" is selected at
"Selection of PV select trigger," the parameter becomes display only.
8)
Displayed when "2-loop/differential temperature control" is selected in "Select function for Input 2" AND "PID control" or
"Heating/Cooling PID control" is selected both in Input 1 and Input 2.
9)
Displayed when "Memory area transfer (without area set signal)" is selected in DI function selection.
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...