172-65419MA-05 (FJ32D-B+BD2) 1 Oct 2021
20
Options
The options shown below are available for this
product on request.
Please compare with the product you received.
Options for Area A (standard: without drain plug)
With Drain Plug
(1 N
m
10 kg
cm)
Part Name
Torque
Distance Across
Flats
N
m
(lbf
·
ft)
mm
(in)
Drain Plug
35
(26)
21
(
13
/
16
)
Options for Area B (screen holder)
With Blowdown Valve (TLV-BD2)
Configuration
TLV Blowdown Valve: BD2
The BD2 Blowdown Valve, installed in the screen area of the connector body, uses the
trap’s internal pressure to blow any condensate, steam, dirt or scale accumulated
around the screen area out to atmosphere.
Always wear eye protection and heat-resistant gloves when operating
the blowdown valve. Failure to do so may result in burns or other injury.
CAUTION
When operating the blowdown valve, stand to the side well clear of the
outlet to avoid contact with internal fluids that will be discharged.
Operate the valve slowly and surely, taking care to avoid the area from
which internal fluids are discharged and any fluids deflected off piping
or the ground etc. Failure to do so may result in burns or other injury.
CAUTION
Do not tighten the BD2 valve or the BD2 valve seat in excess of the
appropriate tightening torque. Over-tightening may cause breakage to
threaded portions, which may cause burns, other injuries or damage.
CAUTION
Do not excessively loosen the BD2 valve when opening the blowdown
valve. The valve stopper pin installed to prevent the BD2 valve from
being removed may break and internal pressure may result in the BD2
valve being blown off, leading to injuries, damage and fluid discharge,
causing burns.
CAUTION
Screen Holder Gasket
BD2 Valve Seat
(Screen Holder)
Screen
Valve Stopper Pin
BD2 Valve
Discharge Hole