172-65378MA-03 (GP10F PowerTrap) 23 Apr 2019
8
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Use hoisting equipment for heavy objects (weighing approximately
20 kg (44 lb) or more). Failure to do so may result in back strain or other
injury if the object should fall.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Do not use excessive force when connecting threaded pipes to the
product. Over-tightening may cause breakage leading to fluid
discharge, which may cause burns or other injury.
CAUTION
Use only under conditions in which no water hammer will occur. The
impact of water hammer may damage the product, leading to fluid
discharge, which may cause burns or other injury.
CAUTION
Open System* Piping (Steam System Example)
P
2
If water hammer due to steam backflow in the condensate recovery line is expected, installation
of a check valve vertically and as close as possible to the recovery line is recommended.
TLV COS/COSR
Pressure Reducing
Valve
TLV CV10 Pressure
Control Valve
P
1
Steam-using
Equipment
Steam Trap
When the rise in piping to the condensate recovery
line is 30 m (100 ft) or further from GP10F,
installation of a check valve is recommended for
the prevention of return water hammer.
Pipe the discharge to a safe area
such as a pit.
TLV
GP10F
Bypass
Valve
Backflow Water Hammer
Prevention Check Valve
Exhaust
Valve
Motive
Medium
Valve
Vent Pipe
Receiver
Filling Head
Standard: 1070 mm (42 in)
Minimum: 860 mm (33 in)
F
las
h S
team
(O
pen t
o at
m
os
pher
e)
P
um
ped M
edium
(
Condens
at
e)
O
ut
let
P
ipe
B
ac
k
flow W
at
er
Ham
m
er
P
rev
ent
ion Chec
k
V
alv
e
O
v
er
flow
H
Pumped Medium
(Condensate)
Recovery Line
Differential
Pressure
Pm - Pb ≥
0.05 MPa
(7 psi)
Pumped Medium Inlet Valve
Pumped Medium Outlet Valve
E
x
haus
t P
ipe
25 m
m
(
1 in)
m
in.
Back Pressure
P
b
= P
2
+ H
Motive Medium Pressure P
m
0.03 to 1.05 MPaG
(5 to 150 psig)
Mot
ive M
edi
um
S
uppl
y P
ipe
20 m
m
(
3
/
4
in)
m
in.
P
um
ped M
edium
(Condens
at
e)
Inlet
P
ipe
Steam Trap
Check Valve
Air Vent
Ball Valve
Strainer
Union
NOTE: This sketch is for explanation purposes only and is not intended as an installation design.