background image

 

172-65454MA-03  (JH7RL-X)    20  Oct  2020 

16

 

 

Steam Discharge 

           

 

Differential Pressure (MPa) 

 
 

         

 

 

 

 

Di

s

c

ha

rge

 Cap

ac

ity

 (

k

g/h

 

Differential Pressure (kg/cm

2

More than 1.5 turns 
1 Turn 
¾ Turn 
½ Turn 
¼ Turn 
 

Number of turns from 
full-closed position 

Differential Pressure (psi) 

Di

s

c

ha

rge

 Cap

ac

ity

 (

lb/h

 

More than 1.5 turns 
1 Turn 
¾ Turn 
½ Turn 
¼ Turn 
 

Number of turns from 
full-closed position 

Содержание JH7RL-X

Страница 1: ...172 65454MA 03 JH7RL X 20 October 2020 Free Float Steam Trap with X element JH7RL X Copyright 2020 by TLV CO LTD All rights reserved ...

Страница 2: ...ture and responds with great accuracy As a result air and the large quantities of condensate created immediately after the start up of operation are quickly discharged thereby greatly reducing start up time and also proving useful in valve operation bypass blowdown labor saving The X element is also sensitive to hot air during operation responding quickly and thus preventing the occurrence of air ...

Страница 3: ...oses a threat of death or serious injury WARNING Indicates that there is a potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment product damage WARNING NEVER apply direct heat to the float The float may explode due to increased internal pressure causing accidents leading to serious injury or damage to property and equipment CAUTION Install...

Страница 4: ...recommended components when repairing the product and NEVER attempt to modify the product in any way Failure to observe these precautions may result in damage to the product and burns or other injury due to malfunction or the discharge of fluids Use only under conditions in which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other injur...

Страница 5: ...ack pressure has a check valve TLV CK been installed 5 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 6 Has the piping work been done correctly as shown in the figures below Requirement Correct Incorrect Install catchpot with the proper diameter Diameter is too small Make sure the flow of condensate is not obs...

Страница 6: ...ising condensate level causes the float to rise due to buoyancy opening the orifice B and allowing condensate to be discharged 3 Hot Air Discharge Should hot air flow into the trap during normal operation the temperature of the X element drops causing it to momentarily contract and open the air vent valve A which allows for the rapid discharge of the air After the air is discharged and steam conta...

Страница 7: ...product nameplate for detailed specifications Model Maximum Allowable Temperature TMA Maximum Allowable Pressure Nominal Diameter Maximum Differential Pressure Production Lot No Valve No Maximum Operating Temperature Maximum allowable pressure PMA and maximum allowable temperature TMA are PRESSURE SHELL DESIGN CONDITIONS NOT OPERATING CONDITIONS Valve No is displayed for products with options This...

Страница 8: ...discharge of fluids CAUTION Installation inspection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel 1 Before installation be sure to remove all protective seals 2 Before installing the product open the inlet valve and blow out the piping to remove any piping scraps dirt and oil Close the inlet valve after blowdown 3 I...

Страница 9: ...th flash steam and the sound of flow can be heard If there is very little condensate there is almost no sound of flow Blocked Discharge Impossible No condensate is discharged The trap is quiet and makes no noise and the surface temperature of the trap is low Blowing Live steam continually flows from the outlet and there is a continuous metallic sound Steam Leakage Live steam is discharged through ...

Страница 10: ...the proper torque Drain Plug Gasket Remove the gasket and clean sealing surface Replace with a new gasket coat surfaces with anti seize Detaching Reattaching the Cover Part During Disassembly During Reassembly Cover Nut Remove with a socket wrench Consult the table of tightening torques and tighten to the proper torque Cover Remove by lifting up and off Make sure there are no pieces of the old gas...

Страница 11: ...ult the table of tightening torques and tighten to the proper torque Orifice Plug Gasket Remove the gasket and clean sealing surface Replace with a new gasket coat surfaces with anti seize Orifice Remove with a socket wrench Consult the table of tightening torques and tighten to the proper torque Orifice Gasket Remove the gasket and clean sealing surface Replace with a new gasket coat surfaces wit...

Страница 12: ... View X element Guide Air Vent Valve Seat Cover Nut Cover Cover Gasket Screen Screen Holder Float Drain Plug Drain Plug Gasket Cover Bolt Body Orifice Gasket Orifice Orifice Plug Gasket Orifice Plug Connector Connector Gasket X element Spring Clip ...

Страница 13: ...e of the plug holder making sure the anti seize affixes the gasket tightly to the plug holder Check to make sure the gasket is not caught in the recesses of the threads 5 Hold the plug holder upside down to make sure that the anti seize makes the gasket stick to the plug holder even when the plug holder is held upside down 6 Screw the plug holder by hand into the product body while making sure tha...

Страница 14: ...eeds the maximum specified pressure or whether there is insufficient pressure differential between the trap inlet and outlet Compare specifications and actual operating conditions Steam is discharged or leaks from the outlet blowing steam leakage Build up on the seating surface of the orifice or rust and scale build up beneath the float Clean parts Scratches on the orifice Replace with a new orifi...

Страница 15: ...oper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to disasters or forces of nature 5 Accidents or malfunctions due to any other cause b...

Страница 16: ...le valve insert a flat head screwdriver into the slot on the top of the needle valve and Open Valve slowly turn counterclockwise Do not continue turning the needle valve past the point at which the snap ring contacts the bottom of the gland case See the table below to determine the amount of steam discharge Close Valve slowly turn clockwise Do not continue turning the needle valve past the point a...

Страница 17: ...e MPa Discharge Capacity kg h Differential Pressure kg cm2 More than 1 5 turns 1 Turn Turn Turn Turn Number of turns from full closed position Differential Pressure psi Discharge Capacity lb h More than 1 5 turns 1 Turn Turn Turn Turn Number of turns from full closed position ...

Отзывы: