172-65639M-01 (EF200) 13 Apr 2018
18
4. Electrical Connection
4.1 Connecting the Transmitter
Warning!
•
Power must be switched off until wiring is completed.
Caution!
•
All relevant national installation regulations must be observed.
•
The power supply is max. 35 V DC.
Procedure (see Fig. 14)
1. Loosen the securing clamp of the connection compartment cover.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry. To ensure tight sealing, do not
remove the sealing ring from the cable entry.
4. Strip the cable and cable ends. In the case of stranded cables, also fit
ferrules.
5. Connect the cable in accordance with the terminal assignment. For HART
communication: when connecting the cable shielding to the ground
terminal, observe the grounding concept of the facility.
6. Firmly tighten the cable glands.
7.
Warning!
Housing protection class may be void due to insufficient sealing of the
housing. Reinsert the screw without using any lubricant. The screw threads
on the cover are coated with a dry lubricant.
Reverse the removal procedure to reassemble the transmitter.
To remove a cable from the terminal, use a flat-blade screwdriver to push
the slot between the two terminal holes while simultaneously pulling the
cable end out of the terminal.
Caution!
Figure 14
Procedure for connecting
the transmitter
Warning!
Warning!