MODEL PS1505 FAN PROVING SWITCH DESIGNED
FOR TJERNLUND AUTO-DRAFT

®

INDUCERS

PURPOSE

SPECIFICATIONS

The Tjernlund PS1505 Fan Prover has been designed to monitor
the pressure within the fan housing only.  A motor or wheel failure
will decrease housing pressure and deactivate the pressure switch,
thus preventing combustion

Voltage: 

125VA pilot duty at 24 volts AC
300VA pilot duty at 115 to 277 volts AC
15 amps non-inductive to 277 volts AC

Electric Switch:

SPST, normally open snap acting contacts

Electric Connectors:

#6-32 screw terminals with cup washer

Control Set Point:

Nonadjustable

Operating Pressure:

On increasing vacuum pressure rise, 

.05 + .02” W.C. with diaphragm in vertical position

Maximum Pressure:

1/2 psi

Operating Temperature Range:

-40

0

to 190

0

F.

Mounting Position:

Diaphragm vertical

Dimensions:

5” diam., 5 1/2” across mounting bracket, 3” high

Weight:

1 Lb. 2 oz.

Finish:

Zinc plated steel

Simple Installation

Mounting Hardware Furnished

Fixed Set Point

TYPICAL OIL WIRING

TYPICAL GAS WIRING

TJERNLUND PRODUCTS, INC.

1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (651) 426-2993 • (800) 255-4208 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com

© 1996 Tjernlund Products, Inc. 

P/N 8500135       Rev. 1 12/96 

FEATURES

TYPICAL INSTALLATION

FLUE PIPE OR BREECHING

1/4” ALUMINUM TUBING

FURNACE PLENUM, WALL OR
JOIST MOUNTING. DIAPHRAGM
MUST BE VERTICAL.

PS1505

SENSING PORT

DRAFT INDUCER