INSTALLATION

ELECTRICAL 

CONNECTION

All electrical work is to be completed by a qualified 
electrician. 

1.  Ensure correct voltage, phase and frequency supply.
2.  Spare capacity of distribution board  shall be 

determined before connecting heat pump.

3.  Circuit breakers,  isolators, cables etc. should be 

selected to meet the continuous operation at “Max 
Current” and handle “Starting Current” for approx 20 
milliseconds (as per this manual, data sheet and heat 
pump nameplate).

4.  Individual isolators are to be installed close to or on 

each heat pump for maintenance purposes.

5.  Tank temp sensor to be appropriately placed (as per 

Tivok Split System manual and installation drawings). 
The temp sensor and controller cables are to be 
connected to the respective labelled cables inside the 
heat pump.

6.  Make sure the wiring, grounding and all terminal 

connections are strong, reliable and appropriate 
for the environmental conditions. All ground line 
connections must be prepared in accordance with 
relevant local regulations.

COMMISSIONING

Commissioning should only be carried out by a qualified 
professional.

1.  Open all the appropriate valves and start filling the 

tank with clean water. 

2.  Bleed all air from heat pump by slowly releasing 

water into the bottom heat pump inlet (return line) 
while keeping the top outlet (supply line) open to the 
atmosphere until only water is released. Slowly filling 
the tank from empty with both heat pump isolation 
valves open will achieve this. If the tank is already full 
then the supply line shouldn’t be connected to the 
tank until all air is bled from the heat pump.

3.  Fill the tank until the refill float valve shuts at the 

upper water limit automatically. The water level inside 
the tank must be at least higher than the heat pump 
outlet line to the tank before starting the heat pump. 
Do not manually fill the tank past the normal refill 
float water level otherwise the float valve may flood 
and continuously leak, refer to Tivok tank installation 
guide for more details.

4.  After the electricity is turned on, turn on the heat 

pump by pressing the on/off key on the controller. 

5.  Check if the fan and the circulation pump are running 

in the right direction. If not, shut down the power 
supply and adjust the phase-order. Make sure the 
compressor current is in a normal range and without 
abnormal sound. 

6.  If the heat pump cycles on / off quickly then there 

could be still air in the heat pump heat exchanger 
thus bleed the remainder of the air and repeat.

7.  Run heat pump continuously and observe for any 

system leakage before thermal insulation is installed

8.  Comprehensively inspect entire system for leakage, 

flow, noise, vibration, heating rate etc. during full cycle 
of tank heating and identify if system is meeting the 
requirements. 

Содержание T-HP38AB

Страница 1: ...Installation and Operation Manual Tivok Energy Heat Pump Models T HP38AB T HP72AB...

Страница 2: ...mp Accessories 9 Water Tank 9 Water Piping 9 Wall mounted Installation 10 Electrical connection 11 Commissioning 11 Controller Operation 12 20 Key Layout 12 LCD Layout 13 Water Temperature setting 14...

Страница 3: ...temperatures from 10 C to 43 C Tivok Energy Heat Pumps are designed for high efficiency performance over the lifetime of operation with an annual average COP of up to 4 5 The water pipes and refrigera...

Страница 4: ...rance NOISE CONTROL Compressor rubber feet are specially selected for reducing vibration and the compressor is fitted with a sound jacket Well balanced fans fan motors and optimized fan holder contrib...

Страница 5: ...Tivok Energy T HP38AB T HP72AB Heat Pump Installation Manual 3 TECHNICAL DATA T HP38AB...

Страница 6: ...Tivok Energy T HP38AB T HP72AB Heat Pump Installation Manual 4 TECHNICAL DATA T HP72AB...

Страница 7: ...Tivok Energy T HP38AB T HP72AB Heat Pump Installation Manual 5 COEFFICIENT OF PERFORMANCE CURVE...

Страница 8: ...Tivok Energy T HP38AB T HP72AB Heat Pump Installation Manual 6 SYSTEM DIAGRAM HEATING MODE DEFROSTING MODE...

Страница 9: ...er is a tube in shell exchanger with a large heat exchanging area and high efficiency for hot water solutions Evaporator The hydrophilic fin tube heat exchanger has a large heat exchanging area and a...

Страница 10: ...e gas or corrosive environments Locate the unit away from falling leaves dust sand and high frequency equipment 6 The unit must be installed on a reliable base or framework Weight capacity of framewor...

Страница 11: ...r circulation pump at least 500mm below the tank water level The heat pump should also be no lower than 2m from the tank This is to maintain a pump suction head of min 700mm Meeting these requirements...

Страница 12: ...plug the controller communication cable 2 Use a screwdriver to open the clip as picture 1 separate the controller into 2 parts as picture 2 below 3 The controller should be installed at eye level on t...

Страница 13: ...t pump inlet return line while keeping the top outlet supply line open to the atmosphere until only water is released Slowly filling the tank from empty with both heat pump isolation valves open will...

Страница 14: ...e value of water temperature clock timer and parameters During failure checking and parameter checking press any of them to exit checking Parameter Setting Press and hold for more than 6 seconds you c...

Страница 15: ...is the corresponding value Water tank temperature symbol the number underneath is the corresponding value Parameter number symbol the number underneath is the corresponding number Heat pump water outl...

Страница 16: ...n the controller will normally display the water tank temperature on the left under TEMP and the heat pump water outlet temperature on the right under OUT Simply press or to adjust water temperature s...

Страница 17: ...3 ON OFF timers can be set at once and recurrence can be set to either everyday default or effective for only one day If timer setting status shows on the bottom the timer is invalid The examples sho...

Страница 18: ...st the hour value Flashing Step 8 Step 9 Flashing Press or to adjust the minute value Step 10 Flashing Step 11 Flashing Press to return to normal display Flash Normal Display Represents one time has b...

Страница 19: ...Flashing Step 5 Flashing Step 6 Flashing Press or to adjust the hour value Flashing Step 8 Step 9 Flashing Press or to adjust the minute value Step 10 Flashing Flashing Step 11 Press to return to nor...

Страница 20: ...P Flashing Flashing Flashing Flashing Flashing Flashing Flashing Flashing Step 4 Step 5 Step 3 Step 7 Step 8 Step 6 Step 10 Step 9 Press or to adjust the minute value Press or to adjust the hour value...

Страница 21: ...one day Running Long press more than 6 seconds Step 1 Standby Step 2 Step 3 Value Press to select the value Adjust the value No 1 represents the incoming electric memorised sign Step 4 Flashing Repres...

Страница 22: ...ancel the timer It demonstrates how to cancel the first timer and can also be repeated for cancelling the 2nd and 3rd timers Step 1 Step 2 Step 3 Step 4 Step 5 Step 7 Step 8 Step 9 Step 10 Step 6 Pres...

Страница 23: ...Tivok Energy T HP38AB T HP72AB Heat Pump Installation Manual 21 WIRING DIAGRAM MODEL T HP38AB T HP72AB...

Страница 24: ...rpressure Check the water pump and valves for proper operation and any leaks Keep the surroundings of the heat pump dry clean and ventilated Regularly clean the evaporator fan forced fin heat exchange...

Страница 25: ...own system 2 EA Refrigerant leak system 1 PF Refrigerant leak system 2 EF High pressure protection Pressure valve break down system 1 E4 High pressure protection Pressure valve break down system 2 E8...

Страница 26: ...HP38AB T HP72AB Heat Pump Installation Manual 24 PARAMETER CHECKING AND RESETTING The system parameters can be checked and adjusted via the controller however they should only be changed by an approv...

Страница 27: ...100 and b for 110 i e A8 is 108 and b8 is 118 For Parameters 13 and 32 the machine off codes are 2 Water tank temp sensor breakdown 3 Evaporator coil temp sensor breakdown 4 Discharge temp sensor brea...

Страница 28: ...hermostatic expansion valve is faulty Change the compressor Compressor is not operating Power source fault Compressor AC contactor damaged Loose wire connection Over heat protection High water tempera...

Страница 29: ...mostatic throttle valve can t start No power to solenoid valve Low water pressure due to small water pipe diameter or long pipe length Inspect the power source of the solenoid valve Check if there is...

Страница 30: ...Tivok Energy T HP38AB T HP72AB Heat Pump Installation Manual 28 Tivok G 04 15 Bourke Rd Mascot NSW 2022 Australia www tivok com au T 6 12 8084 7905 F 6 12 8076 3162 E info tivok com au...

Отзывы: