Titon aura-t B Скачать руководство пользователя страница 1

EN

Commissioning Guide - 

aura-t™ Standard HRV Units

Commissioning Procedure for  

standard HRV HMB & B Units 

 with remote or integral aura-t

Содержание aura-t B

Страница 1: ...EN Commissioning Guide aura t Standard HRV Units Commissioning Procedure for standard HRV HMB B Units with remote or integral aura t ...

Страница 2: ...o reduce the speed when the property is vacant or when on holiday Speed 2 Continuous rate Speed 3 Boost Rate Speed 4 Generally referred to as SummerBoost enables the units speed to be increased when SummerBypass is active Speeds 2 and 3 are generally used to meet the flow rates requirements defined within Approved Document F The following assumes that both Continuous and Boost rates are required i...

Страница 3: ... wet rooms totalling up the measured figures If the total is greater than the required total Extract Boost dwelling rate slow the unit down If the total is less than the required total Extract Boost dwelling rate speed the unit up Keep changing the speed until the total required Extract Boost dwelling rate is achieved As the rates are minimums aim slightly higher approx 1 2 l s Working away from t...

Страница 4: ...welling rate slow the unit down If the total is less than the required total Supply Continuous dwelling rate speed the unit up Keep changing the speed until the total required Supply Continuous dwelling rate is achieved As the rates are minimums aim slightly higher approx 1 2 l s If the reading is excessive it will result in excess noise and increased power consumption Working away from the unit n...

Страница 5: ...s the rates are minimums aim slightly higher approx 1 2 l s If the reading is excessive it will result in excess noise and increased power consumption Press the icon followed by the Extract Supply icon this will put the unit into the Supply Boost setting mode as below The figure pointed at below will be flashing Using the up and down arrows indicated below change the speed to a level that will pro...

Страница 6: ...speeds press the to save and return to the main screen Main screens B Models HMB Models Setting the humidity trigger point and boost overrun timer Press the to enter the set up menu B Models HMB Models If the display has been password protected the screen will show as below if not skip to the next instruction ...

Страница 7: ... The screen will show as below press the icon to progress to the commissioning screen B Model Press the up arrow shown below twice until the screen looks like the one below on the right with the humidity figure flashing HMB Model Will show with humidity figure flashing All models Press the icon shown below ...

Страница 8: ...en will display as below with the humidity figure flashing Use the up and down arrows to change the percentage as below Once the required figure has been set press the icon as shown below The screen will look as below To return to the main screen press icon To set the Overrun timer read on ...

Страница 9: ...f the switch inputs are set accordingly The Kitchen overrun timer time will be flashing as indicated below Press the and the screen will look as below with the Kitchen overrun timer will be flashing as indicated below Press the and the screen will look as below with the wet room overrun timer flashing as indicated below Press the and the screen will look as below with the wet room overrun timer fl...

Страница 10: ...the up and down arrow keys change the time to the required setting in minutes Once the required setting has been set press the icon the screen will look as below To return to the main screen press Other settings can be accessed please see the respective aura t manuals url link for details ...

Страница 11: ...11 Sales and Technical Support 44 0 1206 713801 enquiries titon com www titon com ...

Страница 12: ...plete This Product Manual must be kept in the Home Information Pack and used as a service record Important environmental information about this product This symbol on this unit or the package indicates that disposal of this unit after its life cycle could harm the environment Do not dispose the unit as unsorted municipal waste it should be disposed by a specialized company for recycling This unit ...

Отзывы: