HERCULES

®

 Low Voltage Contact Module

REASON TO USE A LOW VOLTAGE CONTACT MODULE: 

This module is designed to interface any “120V output” to Air Conditioning/Heating “Low Voltage Control Inputs.” 
Some Titan Controls

®

 Controllers have “120V outputs” (eg. Apollo

®

 series timerZephyr

®

 series controllersEos

®

 series controllers

Atlas

®

 series controllers … ). Should you need to control any SYSTEM whose inputs are not compatible with 120V output power,  

you must use this module and refer to the connection diagram in the USER GUIDE of the SYSTEM you want to control.

ELECTRICAL SPECIFICATIONS: 

Input: Low Power Coil - 120V AC 60HZ 0.4W 

Output: Low Power Contact - 5A at 24V DC / 120V AC MAX.

•  COM is the relay COMMON

•  N.O. is the NORMALLY OPEN contact

•  N.C. is the NORMALLY CLOSED contact

MECHANICAL SPECIFICATIONS: 

Plastic enclosure dimensions: length 2 inches, width 1.5 inch, 

depth 1 inch, prong length 0.65 inch 

Terminal: thick Brass, Tin Plated 

Screws: 6-32, length 0.25 inch

(120V Prongs  

connect to  

the Coil)

120V

60HZ

Coil

N.O.

N.C.

COM

TYPICAL CONNECTION DIAGRAM: 

Here is a typical connection diagram between 

Hercules

®

 Low Voltage Contact Module and any Air Conditioning System. Main  

power to the A/C System is not shown here, only A/C control input terminals need to be connected to the 

Hercules

®

 Low Voltage 

Contact Module

SYSTEM 

Eg. A/C System similar to  

many mainstream models.

MODULE 

Hercules

®

 Low Voltage  

Contact Module To  

connect into Titan Controls

®

  

Controller Outputs 

N.O. COM N.C.

R

W

Y

G

LOW VOLTAGE CONTROL INPUTS ON TYPICAL HEATING OR COOLING SYSTEM: 

When using the 

Hercules

®

, power lines to the SYSTEM, it must be connected directly to the building electrical box. Control inputs are  

normally available on a SCREW TERMINAL BLOCK, each SYSTEM IN’s or OUT’s being identified by a letter. Typically, SYSTEM OUT 

LINES will connect to the 

Hercules

®

 “COM” screw terminal and SYSTEM IN LINES to the 

Hercules

®

 ‘’N.O.” screw terminal. 

Typically, System OUTPUTS are connected to Hercules

®

 “COM” screw terminal.       Typically, System INPUTS are connected to Hercules

®

 “N.O.” screw terminal.

OUTPUTS

Description

INPUTS

Description

R

24Vac Power to connect to any “INPUTS”

Y or Y1

Single or First Stage Cooling

Rh

24Vac Power to connect to W / W1 / W2 / G

Y2

Optional Second Stage Cooling

Rc

24Vac Power to connect to Y / Y1 / Y2 / G

W or W1

Single or First Stage Heating

C

24Vac Common, generally not used 

W2

Optional Second Stage Heating

Note: SYSTEM normally provides either “R” only or “Rh and 

Rc”. Rh is for Heating inputs (W), Rc for cooling inputs (Y). 

G

Fan

Warranty = 1 Year

www.titancontrols.net

For technical assistance call us at

1-888-80-Titan or 1-888-808-4826.