16. The system will automatically shut off the Pilot valve and the Main valve when the heater is
tipped over, or the power supply voltage is lower than 90 V AC. The indicators on the panel will
flash. The system will restart the ignition sequence again after the fault has been resolved for 10
seconds.
17. Automatic recycle: The system will perform a self-check for 5 seconds when the heater
remains in the running position for 1 hour. If no fault is found, the system will automatically restart
the ignition sequence every hour.
18. Automatic Electrical Burner Control System Working Time Sequence:

Step

 

Go to

 

If Yes, 

go to

 

If No, 

go to

 

1

 

Power ON

 

2

 

2

 

Safe start check

 

3

 

16

 

3

 

Initiating ignition sequence, heating the ignitor for 3sec

 

4

 

4

 

Open the Pilot valve for 11 sec

 

5

 

5

 

Pilot flame detector detecting the presence of flame

 

6

 

18

 

6

 

Open the Main valve for 4 sec, and turn off the ignitor

 

7

 

7

 

Main flame detector detecting the presence of flame

 

8

 

22

 

8

 

Establish the main flame

 

9

 

9

 

Check the flame detector’s working status

 

10

 

16

 

10

 

Check power supply voltage and tip-over switch’s 

working status

 

11

 

14

 

11

 

Check the presence of flame during the running 

position

 

13

 

12

 

12

 

Allow to run for 1 hour

 

2

 

9

 

13

 

Start the ignition sequence and check for the presence 

of flame after 6 sec

 

8

 

2

 

14

 

Shut off all fuel supplies

 

15

 

15

 

Check the power supply voltage and tip-over switch for 

10 sec

 

2

 

14

 

16

 

System lock-out, fault indicator

 

17

 

17

 

Reset the system by long pressing the Reset button

 

2

 

16

 

18

 

5 ignition attempts for Pilot flame, main valve will be 

energized at 2nd/5th attempt in first cycle

 

20

 

19

 

19

 

Keep the ignitor working and turn the Pilot valve on for 

11 seconds

 

5

 

20

 

Shut off the Main valve, Pilot valve. Keep the ignitor 

working, it repeats the 4 cycles

 

16

 

21

 

21

 

30 sec of purge time, start a new Pilot flame 

establishing cycle after purge time

 

3

 

22

 

After 4 failed ignition attempts, the system 

automatically enters step 16

 

16

 

23

 

23

 

Wait for 12sec

 

6

 

Содержание HAWTHORNE ARES

Страница 1: ...low ANSI Z21 11 2 19 Gas fired Unvented Room Heaters RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING PERSONNEL Prior to installation thoroughly familiarize yourself with this Install...

Страница 2: ...LP NG Ares Garden Heater Ares Garden Heater Specifications Installation Instructions Operating Procedures for Ares Garden Heater Operating Procedures for Atlas CO2 Controller with Low Oxygen Shutoff...

Страница 3: ...NY 3204 NW 38th Cir Vancouver WA 98660 United States This product has two important parts that need to be replaced every year Oxygen Sensor and Silicon Nitride Hot Surface Igniter Please contact servi...

Страница 4: ...on pin connecting terminal B remove the metal clip C and remove the old ignition pin D 3 Replace the new ignition pin D and then connect the terminal B insert the new ignition pin back to the original...

Страница 5: ...from combustible materials gasoline and other flammable vapors and liquids WARNING FIRE EXPLOSION AND ASPHYXIATION HAZARD Improper adjustment alteration service maintenance or installation of this hea...

Страница 6: ...h connection do not use mobile phones lighters and other items that may ignite and wait for a period of time to ensure that the flammable gas accumulated in the machine and the surrounding area is ful...

Страница 7: ...dioxide and limit or control the concentration of carbon dioxide by using an Ares Garden Heater and Atlas CO2 Controller with Oxygen Shutoff Hard wire in an unvented area When the oxygen concentratio...

Страница 8: ...urner operation The pilot is automatically extinguished when each main burner operating cycle is completed The ignition source is automatically de energized when the pilot flame is established Lock ou...

Страница 9: ...ocking airflow and provide adequate clearances for accessibility for servicing and proper operation Keep the environment well ventilated The heater shall not be installed on a combustible solid suppor...

Страница 10: ...rify that you are connecting the proper gas source for your type of heater LP or NG 3 Connect the proper gas supply source for your heater verify that it is the proper pressure by referring to table p...

Страница 11: ...iod Before the pilot flame has been successfully established the system will make 5 ignition attempts with an interval of 11 seconds between each attempt The system will perform this cycle a maximum o...

Страница 12: ...the ignitor 7 7 Main flame detector detecting the presence of flame 8 22 8 Establish the main flame 9 9 Check the flame detector s working status 10 16 10 Check power supply voltage and tip over swit...

Страница 13: ...ck Out If the communication between the master MCU and the monitor MCU times out the controller will also lock out Automatic self checking every 1 hour 19 If the Main flame has been successfully estab...

Страница 14: ...ot and burner flame periodically If the flame is yellow and large please cut off the power immediately to confirm whether it is the correct gas source 5 If the flame is yellow there may be insufficien...

Страница 15: ...15...

Страница 16: ...90 V AC 5 V the system will resume operation after the voltage is restored for 10 sec 4 MAIN Power On Lock Out error Main Valve On Pilot Valve On ON ON Flashing OFF System Lock Out Main flame valve fa...

Страница 17: ...w Oxygen Shutoff controller is designed to allow you to accurately reach your desired CO2 levels It features a remote sensor with a 15ft cord that contains a CO2 sensor O2 and a photocell If the oxyge...

Страница 18: ...inimum and maximum of recorded CO2 The second screen shows the recorded Min Max Recall of O2 minimum and maximum Can only read the minimum value and maximum value of the past period of time press both...

Страница 19: ...CO2 PPM Garden Heater Deadband Setpoint On Off Time 8 Specifications Power 120 V AC 60 Hz 1A CO2 range 400 2000 PPM CO2 accuracy 100 PPM O2 range 0 25 O2 accuracy 2 9 CO2 Control Logic Diagram Product...

Страница 20: ...20 Regulator Valve manual switch Turn clockwise to close counterclockwise to open Back Front Back...

Страница 21: ...icing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Module decomposition diagram Housing Modules Atlas CO2 controller with Low Oxygen Shutof...

Страница 22: ...22 260 Dimensioned Production Drawings 500 86 8 500 30 16 420 399 14 426 196 36 750 28...

Страница 23: ...23 Note If any of the original wire as supplied with the appliance must be replaced it must be replaced with a wire of at least a temperature rating...

Страница 24: ...2424 23 Note If any of the original wire as supplied with the appliance must be replaced it must be replaced with a wire of at least a temperature rating 24...

Страница 25: ...s no warranty whatsoever in respect to accessories or parts not supplied by Titan Controls Monetary refunds of the warranty will not be given The Buyer assumes all responsibility regarding the use ins...

Страница 26: ...n Number Required ___________________________________________ Company Name ____________________________________________________________________________________ Contact Name ___________________________...

Страница 27: ...27 Notes 1 Square ____ Foot Feet...

Страница 28: ...itan Controls LB17721 titancontrols net Manufactured for Hawthorne Hydroponics LLC a subsidiary of The Hawthorne Gardening Company 3204 NW 38th Circle Vancouver WA 98660 HawthorneGC com 2021 World rig...

Отзывы: