background image

6

ELECTRICAL REQUIREMENTS AND 

INSTALLATION

The following information is provided for hooking up electrical supply to 

your new pool. A qualified, licensed, electrician must perform this work. 

Failure to follow these instructions will terminate all warranty coverage 
and can cause serious injury or death.

Your 60 Hz pool is preset at the factory to run on 240 V with a 48 A input. 
This feature gives you the most performance out of your pool. This will 
require a 240 V, 60-amp GFCI 

Your export 50 Hz pool is preset out of factory to run 230 V-240 V 3 
wires 30 A max input.  This product must always be connected to resid-
ual current device (RCD) having a trip current of not more than 30 mA.

ELECTRICAL WIRING

WARNING:  Your pool must be wired by a certified electrician and 

according to these  instructions. Failure to do so will terminate all 

warranties and all listings from the independent listing facility.

1) The TidalFit requires a 240 VAC dedicated system. The pool must be 
hard wired to the power supply, with no plug-in connections, extension 
cords, or sharing of service.

2) The pool requires that you run 6 (10 mm²) or 8 (8.4 mm²)  AWG cop-
per wire, depending on the GFCI size. Do Not Use Aluminum Wire.

3) The power supply must have a suitable Ground Fault  Circuit Inter-
rupter (GFCI), according to Section 422-20 of the National Electrical 
Code, ANSI/NFPA 70-7987 or other national installation requirement 
with a residual current device (RCD) having a trip current of not more 
than 30 mA.  This could be used as the shut-off switch, which must be 
installed in plain view of the pool. This electrical service must be readily 
accessible to the pool occupants, but must not be within 5 feet of the 
pool. 

4) Use only non-metallic conduit and fittings when installing power to 

the spa.

5) After your pool has been positioned, route lines through the knockout  
on the left or right front corner of the pool.

6) Connect the power to the pool.

Отзывы: