TECHNICAL DATA
33
I
LR
>> Element
CLP operating mode (
Mode 51LR>>
)
With/without speed control
CLP activation time (
t
LRCLP>>
)
21
24
0.00...200 s
0.00...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Definite time
Second threshold definite time (
I
LR
>>
def
) 0.90...8.00
I
B
(step 0.01
I
B
)
Operating time (
t
LR
>>
def
)
0.10...200
s
0.10...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
0.5% with 0.1
I
n
±
0.2% with 1
I
n
Operate time accuracy
5% ± 10 ms
—
Voltage-controlled / restraint overcurrent - 51V
Common configuration:
Operating mode (
Mode51V
)
Voltage
controlled
Voltage
restraint
Voltage restraint threshold (
U
-I/U
<)
0.10...1.00
U
n
(step 0.01
U
n
)
Voltage controlled first threshold (
U
-I/U-1
<)
0.10...1.00
U
n
(step 0.01
U
n
)
Voltage controlled second threshold (
U
-I/U-2
<)
0.10...1.00
U
n
(step 0.01
U
n
)
Reduction factor (
K
)
0.10...1.00 (step 0.01)
I
-I/U>
Element
Reset time delay (
t
-
I/U>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
First threshold definite time (
I
-
I/U>def
)
0.20...10.00
I
n
(step 0.01
I
n
)
Operating time (
t
-I/U>def
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
I
-I/U>>
Element
Reset time delay (
t
-
I/U>>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
Second threshold definite time (
I
-
I/U>>def
) 0.20...20.00
I
n
(step 0.01
I
n
)
Operating time (
t
-I/U>>def
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
0.5% on current measures
±
0.5% on voltage measures
Operate time accuracy
5% ± 10 ms
—
Residual overcurrent - 50N/51N or High impedance restricted earth fault - 87NHIZ
IE> Element
Curve type (
I
E
>
Curve
)
DEFINITE,
IEC/BS A, B, C,
ANSI/IEEE MI, VI, EI, LIT, EM
CLP operating mode (
I
ECLP
>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time (
t
ECLP>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
E
>
RES
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
First threshold definite time (
I
E
>
def
)
0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
I
E
>
def
within CLP (
I
ECLP>def
) 0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
n
(step 0.01
I
En
)
Note 21 The element is blocked for the t
LRCLP
time (an adjustable threshold active during CLP does not exist)
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021