TECHNICAL DATA
A3-A4 Terminals polarity (A3-A4 POL)
NORMAL/REVERSE
A5-A6 Terminals polarity (A5-A6 POL)
NORMAL/REVERSE
A7-A8 Terminals polarity (A7-A8 POL)
NORMAL/REVERSE
B3-B4 Terminals polarity (B3-B4 POL)
NORMAL/REVERSE
B5-B6 Terminals polarity (B5-B6 POL)
NORMAL/REVERSE
B7-B8 Terminals polarity (B7-B8 POL)
NORMAL/REVERSE
B9-B10 Terminals polarity (B9-B10 POL)
NORMAL/REVERSE
—
Line
7
Line positive sequence resistance value (
R
1L
)
0.05...200
m
Z
NF
/km
0.05...0.99 m
Z
NF
/km (step 0.01 m
Z
NF
/km)
1.0...9.9 m
Z
NF
/km (step 0.1 m
Z
NF
/km)
10...200 m
Z
NF
/km (step 1 m
Z
NF
/km)
Line positive sequence reactance value (
X
1L
)
0.05...200
m
Z
NF
/km
0.05...0.99 m
Z
NF
/km (step 0.01 m
Z
NF
/km)
1.0...9.9 m
Z
NF
/km (step 0.1 m
Z
NF
/km)
10...200 m
Z
NF
/km (step 1 m
Z
NF
/km)
Line zero sequence resistance valuee (
R
0L
)
0.05...200 m
Z
NF
/km
0.05...0.99 m
Z
NF
/km (step 0.01 m
Z
NF
/km)
1.0...9.9 m
Z
NF
/km (step 0.1 m
Z
NF
/km)
10...200 m
Z
NF
/km (step 1 m
Z
NF
/km)
Line zero sequence reactance value (
X
0L
) 0.05...200
m
Z
NF
/km
0.05...0.99 m
Z
NF
/km (step 0.01 m
Z
NF
/km)
1.0...9.9 m
Z
NF
/km (step 0.1 m
Z
NF
/km)
10...200 m
Z
NF
/km (step 1 m
Z
NF
/km)
Line length (
L
)
0.1...1000.0 km (step 0.1 km)
—
Starting control set
CLP input source (
CLP Source
)
IRUN/CB
IRUN Threshold (
I
RUN
)
0.10
I
B
3.7
PROTECTIVE FUNCTIONS
—
Base current - IB
Base current (
I
B
)
8
0.10...2.50
I
n
(step 0.01
I
n
)
—
Underimpedance - 21
Z< Element
Definite time
First threshold definite time (
Z
<
def
)
0.02...3.00
Z
n
9
(step 0.01
Z
n
)
Operate time (
t
Zdef
<)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
Z
<
RES
)
0.00...100.0
s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Z<< Element
Definite time
Second threshold definite time (
Z
<<
def
)
0.02...3.00
Z
n
[2]
(step 0.01
Z
n
)
Operate time (
t
Zdef
<<)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
Z
<<
RES
)
0.00...100.0
s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤ 0.04 s
Dropout
ratio
1.03...1.05
Dropout time
≤ 0.05 s
Overshoot time
0.03 s
Reference values
rest: 1.5
I
T
trip:
0.5
I
T
10
Pickup
accuracy ±
4% ±
0.5%
Z
n
Operate time accuracy
5% or ± 10 ms
—
Overeflux- 24
(U/f)AL Element
Definite time
Alarm threshold definite time (
U/f
)
AL
0.50...2.00
U
n
/f
n
(step 0.01
U
n
/f
n
)
U/f)ALdef Operating time (
t
(U/f)ALdef
)
0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Note 7 The parameters concern the fault location function (FL)
Note 8 The base current I
B
represents the rated current of the line or transformer, referred to the nominal current of the CT’s for thermal image protection.
Note 9 Zn is the impedance given by the ratio between the relay rated voltage relay (U