36
36
SIF5600 - Manual - 03 - 2008
I/O block
the following information is made available in relation to the accelerated logic:
Blin1
On
Logic state of the Blin1 block input circuit (in the example - ON)
Blout1, Blout2 On
Logic state of the block output circuits (in the example - ON)
Status 52
the following information is made available in relation to the breaker status (52):
Status 52
Open Breaker status (Unknown if check 52 is disabled)
52b
On
Logic state of the auxiliary circuit 52b
52a
Off
Logic state of the auxiliary circuit 52b
Counters
trip counters
the number of operations (StArtS and/or trIPS) are counted separately for each protective func-
tion.
the count relating to the number of operations is stored permanently in appropriate resettable four
digit counters (0...9999); at the ten thousandth operation, the count will restart from zero.
the following information is available:
counter St I>
2
Maximum overcurrent function start counter
counter St I>>
3
Short-circuit function start counter
counter St Ie>
4
Ground fault function first threshold start counter
counter St Ie>>
5
Ground fault function second threshold start counter
counter tr I>
1
Maximum overcurrent function trip counter
counter tr I>>
2
Short-circuit function trip counter
counter tr Ie>
3
Ground fault function first threshold trip counter
counter tr Ie>>
4
Ground fault function second threshold trip counter
Events
Values of the variables relating to the last eight operations (StArtS or trIPS)
the value of the following input quantities are stored at the instant immediately prior to the trip of
the protective device for a function active on a output relay. the storage buffer is circular in nature
whereby the data relating to the events subsequent to the first eight overwrite the data pertaining
to the preceding events. to identify the time sequence of the stored events, there is an index (1...8)
which identifies the latest event in chronological order.
the function which caused the trip is stored, in addition, in the case of I>, I>> functions, then also the
phase (or phases) exceeding the intervention threshold is recorded.
the following information is available:
Info
events stored (number of events in memory)
event1
e1 reading
Direct (type of reading - Direct)
e1 IL1r 15.424 A/In
(L1 phase current value)
e1 IL2r 15.424 A/In
(L2 phase current value)
e1 IL3r 15.424 A/In
(L3 phase current value)
e1 Ier 0.00000 A/In (residual current value)
e1 cause
trip I> (function responsible for the intervention)
e1 Phases
IL1
(phases on which the current was detected).
NB if the currents are in relation to two or more phases, then they are viewed on the display in
sequence
e1 Blin1r
Off
(Block input status)
e1 Blout1-2rr Off
(Block output status)
e1 Year
2000 (Year)
e1 Month
1
(Month)
e1 Day
1
(Day)
e1 Hour
1
(Hour)
e1 Minute
55
(Minute)
e1 Second
23
(Seconds)
e1 Millisecond 61
(Milliseconds)
event2
e2 reading
......................
event3
e3 reading
......................
event4
e4 reading
......................
event5
e5 reading
......................
event6
e6 reading
......................
event7
e7 reading
......................
event8
e8 reading
......................