PRON NA60-CB0
Version 2.00
Page: 6 of 15
PRON NA60-CB0 IEC 870-5-103
<82>
Zone 5
<83>
Zone 6
<84>
General start/pick-up
<85>
Breaker failure
<86>
Trip measuring system L
1
<87>
Trip measuring system L
2
<88>
Trip measuring system L
3
<89>
Trip measuring system E
<90>
Trip I>
<91>
Trip I>>
<92>
Trip IN>
<93>
Trip IN>>
8.3.3.6 Auto-reclosure indications in monitor direction
INF
Semantics
<128>
CB 'on' by AR
<129>
CB 'on' by long-time AR
<130>
AR blocked
8.3.3.7 Measurands in monitor direction
INF
Semantics
<144>
Measurand I
<145>
Measurands I, V
<146>
Measurands I, V, P, Q
<147>
Measurands I
N
, V
EN
<148>
Measurands I
L1,2,3
, V
L1,2,3
, P, Q, f
8.3.3.8 Generic functions in monitor direction
INF
Semantics
<240>
Read headings of all defined groups
<241>
Read values or attributes of all entries of one group
<243>
Read directory of a single entry
<244>
Read value or attribute of a single entry
<245>
End of general interrogation of generic data
<249>
Write entry with confirmation
<250>
Write entry with execution
<251>
Write entry aborted