PRON NA60-CB0

 

 

Version 2.00 

 

 

Page: 11 of 15 

 

PRON NA60-CB0 IEC 870-5-103 

 

2.11 List of events produced by the relay 

Two kinds of ASDU can be generated for the events :  
Type ASDU 1 (time-tagged message) 
Type ASDU 2 (Time-tagged message with relative time) 

 
 

LIST OF FAULTS 

  

  

  

  

  

  

  

  

  

DSC 

NAME 

NORMALIZE 
FACTOR 

RATED 
VALUE 

FUN  INF 

TYP

COT  BIDI 

CAA 

Trip I>  

TRIP_IM 

160  90 

Trip I>>  

TRIP_IMM 

160  91 

Trip I>>>  

TRIP_IMMM 

160  94 

Trip IE>  

TRIP_INM 

162  92 

Trip IE>>  

TRIP_INMM 

162  93 

Trip IE>>>  

TRIP_INMMM 

162  96 

Trip U<  

TRIP_IM 

165  90 

Trip U<<  

TRIP_IMM 

165  91 

Trip U>  

TRIP_IM 

166  90 

Trip U>>  

TRIP_IMM 

166  91 

Trip UE>  

TRIP_INM 

167  92 

Trip UE>>  

TRIP_INMM 

167  93 

Trip Dth>  

TRIP_IM 

168  90 

Trip IPD>  

TRIP_IM 

163  90 

Trip IPD>>  

TRIP_IMM 

163  91 

Trip IPD>>>  

TRIP_IMMM 

163  94 

Trip IPD>>>>  

TRIP_IMMMM 

163  95 

Trip IED>  

TRIP_INM 

164  92 

Trip IED>>  

TRIP_INMM 

164  93 

Trip IED>>>  

TRIP_INMMM 

164  96 

Trip IED>>>>  

TRIP_INMMMM 

164  97 

Alarm ThAL1  

ALARM_PT1 

178  198  2 

Trip Th>1  

TRIP_PT1 

178  199  2 

Alarm ThAL2  

ALARM_PT2 

178  200  2 

Trip Th>2  

TRIP_PT2 

178  201  2 

Alarm ThAL3  

ALARM_PT3 

178  202  2 

Trip Th>3  

TRIP_PT3 

178  203  2 

Alarm ThAL4  

ALARM_PT4 

178  204  2 

Trip Th>4  

TRIP_PT4 

178  205  2 

Alarm ThAL5  

ALARM_PT5 

178  206  2 

Trip Th>5  

TRIP_PT5 

178  207  2 

Alarm ThAL6  

ALARM_PT6 

178  208  2 

Trip Th>6  

TRIP_PT6 

178  209  2 

Alarm ThAL7  

ALARM_PT7 

178  210  2 

Trip Th>7  

TRIP_PT7 

178  211  2 

Alarm ThAL8  

ALARM_PT8 

178  212  2 

Trip Th>8  

TRIP_PT8 

178  213  2 

Trip 74TCS  

TC_SUPERVISION 

255  36 

Trip BF  

BF 

255  85 

 

Содержание PRON NA60-CB0

Страница 1: ...Version 2 00 Page 1 of 15 PRON NA60 CB0 IEC 870 5 103 PRON NA60 CB0 IEC 870 5 103 Communication Protocol User Guide PRON NA60 CB0 ...

Страница 2: ...rection 4 8 3 4 Selection of standard information numbers in control direction 7 8 3 5 Basic application functions 7 8 3 6 Miscellaneous 8 2 IEC60870 5 103 INTERFACE 8 2 1 Physical connection and link layer 8 2 2 Initialisation 9 2 3 Time synchronisation 9 2 4 Spontaneous events 9 2 5 General interrogation 9 2 6 Cyclic measurements 9 2 7 Commands 10 2 8 Disturbance records 10 2 9 Blocking of monit...

Страница 3: ...urposely retained from that document for reference 8 INTEROPERABILITY 8 1 Physical Layer 8 1 1 Electrical Interface EIA RS 485 Number of loads 32 For one protection equipment NOTE EIA RS 485 standard defines unit loads so that 32 of them can be operated on one line For detailed information refer to clause 3 of EIA RS 485 standard 8 1 2 Optical Interface Glass fibre Plastic fibre F SMA type connect...

Страница 4: ... of standard information numbers in monitor direction 8 3 3 1 System functions in monitor direction INF Semantics 0 End of general interrogation 0 Time synchronization 2 Reset FCB 3 Reset CU 4 Start restart 5 Power on 8 3 3 2 Status indications in monitor direction INF Semantics 16 Auto recloser active 17 Teleprotection active 18 Protection active 19 LED reset 20 Monitor direction blocked 21 Test ...

Страница 5: ... indications in monitor direction INF Semantics 48 Earth fault L1 49 Earth fault L2 50 Earth fault L3 51 Earth fault forward i e line 52 Earth fault reverse i e busbar 8 3 3 5 Fault indications in monitor direction INF Semantics 64 Start pick up L1 65 Start pick up L2 66 Start pick up L3 67 Start pick up N 68 General trip 69 Trip L1 70 Trip L2 71 Trip L3 72 Trip I back up operation 73 Fault locati...

Страница 6: ...by long time AR 130 AR blocked 8 3 3 7 Measurands in monitor direction INF Semantics 144 Measurand I 145 Measurands I V 146 Measurands I V P Q 147 Measurands IN VEN 148 Measurands IL1 2 3 V L1 2 3 P Q f 8 3 3 8 Generic functions in monitor direction INF Semantics 240 Read headings of all defined groups 241 Read values or attributes of all entries of one group 243 Read directory of a single entry 2...

Страница 7: ...e characteristic 1 24 Activate characteristic 2 25 Activate characteristic 3 26 Activate characteristic 4 8 3 4 3 Generic functions in control direction INF Semantics 240 Read headings of all defined groups 241 Read values or attributes of all entries in one group 243 Read directory of a single entry 244 Read value or attribute of a single entry 245 General interrogation of generic data 248 Write ...

Страница 8: ...Voltage L1 L2 2 IEC60870 5 103 INTERFACE The following IEC60870 5 103 facilities are supported by this interface 1 Initialisation 2 Time Synchronisation 3 Event Record Extraction 4 General Interrogation 5 Cyclic Measurements 6 General Commands 2 1 Physical connection and link layer Connection is available for IEC60870 5 103 through the rear RS485 port It is possible to select both the relay addres...

Страница 9: ... numbers to the IEC60870 5 103 master station Private codes are not used thus any events that cannot be passed using the standardised messages will not be sent Events are categorised using the following information Common Address Function Type Information number The common address is used to differentiate in circumstances where the relay produces more events of a certain type than can be passed us...

Страница 10: ...T of negative acknowledgement of a command 2 8 Disturbance records The relay does not support the exchange of disturbance data through the mechanism defined in the IEC60870 5 103 standard 2 9 Blocking of monitor direction The relay does not support a facility to block messages in the Monitor direction 2 10Acronyms FUN Function Type INF Information Number TYPE Type of ASDU COT Cause of Transmission...

Страница 11: ...IP_IM 168 90 2 1 3 Trip IPD TRIP_IM 163 90 2 1 3 Trip IPD TRIP_IMM 163 91 2 1 3 Trip IPD TRIP_IMMM 163 94 2 1 3 Trip IPD TRIP_IMMMM 163 95 2 1 3 Trip IED TRIP_INM 164 92 2 1 3 Trip IED TRIP_INMM 164 93 2 1 3 Trip IED TRIP_INMMM 164 96 2 1 3 Trip IED TRIP_INMMMM 164 97 2 1 3 Alarm ThAL1 ALARM_PT1 178 198 2 1 3 Trip Th 1 TRIP_PT1 178 199 2 1 3 Alarm ThAL2 ALARM_PT2 178 200 2 1 3 Trip Th 2 TRIP_PT2 1...

Страница 12: ...NPUT_18 255 173 1 1 X 3 IN19 AUX_INPUT_19 255 174 1 1 X 3 IN20 AUX_INPUT_20 255 175 1 1 X 3 IN21 AUX_INPUT_21 255 176 1 1 X 3 IN22 AUX_INPUT_22 255 177 1 1 X 3 IN23 AUX_INPUT_23 255 178 1 1 X 3 IN24 AUX_INPUT_24 255 179 1 1 X 3 IN25 AUX_INPUT_25 255 180 1 1 X 3 IN26 AUX_INPUT_26 255 181 1 1 X 3 IN27 AUX_INPUT_27 255 182 1 1 X 3 IN28 AUX_INPUT_28 255 183 1 1 X 3 IN29 AUX_INPUT_29 255 184 1 1 X 3 IN...

Страница 13: ...169 1 9 3 IN15 AUX_INPUT_15 255 170 1 9 3 IN16 AUX_INPUT_16 255 171 1 9 3 IN17 AUX_INPUT_17 255 172 1 9 3 IN18 AUX_INPUT_18 255 173 1 9 3 IN19 AUX_INPUT_19 255 174 1 9 3 IN20 AUX_INPUT_20 255 175 1 9 3 IN21 AUX_INPUT_21 255 176 1 9 3 IN22 AUX_INPUT_22 255 177 1 9 3 IN23 AUX_INPUT_23 255 178 1 9 3 IN24 AUX_INPUT_24 255 179 1 9 3 IN25 AUX_INPUT_25 255 180 1 9 3 IN26 AUX_INPUT_26 255 181 1 9 3 IN27 A...

Страница 14: ...SET1 2 4 Un 169 149 9 11 2 3 U23 MEASURAND_SET1 2 4 Un 169 149 9 12 2 3 U31 MEASURAND_SET1 2 4 Un 169 149 9 13 2 3 UEC MEASURAND_SET1 2 4 UECn 169 149 9 14 2 3 Alpha1 MEASURAND_SET1 2 4 180 169 149 9 15 2 3 Alpha2 MEASURAND_SET1 2 4 180 169 149 9 16 2 3 Alpha3 MEASURAND_SET2 2 4 180 169 150 9 1 2 3 PhiE MEASURAND_SET2 2 4 180 169 150 9 2 2 3 PhiEC MEASURAND_SET2 2 4 180 169 150 9 3 2 3 P MEASURAND...

Страница 15: ...0 Page 15 of 15 PRON NA60 CB0 IEC 870 5 103 2 14List of the supported commands LIST OF COMMANDS DSC NAME NORMALIZE FACTOR RATED VALUE FUN INF TYPE COT CAA LED_RESET 254 19 20 20 3 OPEN_CB 254 32 20 20 3 CLOSE_CB 254 33 20 20 3 ...

Отзывы: