Thytronic NVA100X Скачать руководство пользователя страница 13

13

NVA100X - Getting started - 01 - 2018

 

TEST

The operational tests with command of the selected output relays may be activated.
By means of  

 (Up) or 

 (Down) buttons it is possible to browse the main menu till the “ “

TEST

” 

message; to enter you must press the 

 (Right) button. 

[1]

 The display message “

Test  state: 

OFF

” shows the test state (OFF or test in progress).

By means of  

 (Down) button is possible to browse menu to select:

• Stop test

• Start test

• Test KC1-1

• Test KC1-2

• Test KC1-3

• Test K...

As example, to start the test of KC1-1, the following procedure must be issued::

• Select the Start test menu “

Start test? >>

”.

• Press the 

 (Right) button to start; the test in progress status is highlighted by activation of all LEDs.

• Come back by pressing the 

 (Left) .

• Select the relay to be tested KC1-1 by means    or   until the message “

Test KC1-1? >> 

is displayed.

• Press the 

 (Right) button to start the test on KC1-1.

• To terminate the test, it is necessary to select the “

Stop test? >>

” message and press the  

 

(Right). button to end the test. In any case the test will be automatically terminated after a delay of 

one minute.

 

COMMUNICATION

Inside the 

COMMUNICATION

 menu it is possible to read/modify the setting data of the RS485 Protocol

and Ethernet parameters. Since newer versions Ip Address can be modified only in 

Commands \ Set 

Params \ Set not resettable parameter

.

By means of 

  (Up) or 

  (Down)  buttons it is possible to browse the main menu till the “

RS485 

Protocol >>

”, “

Ethernet Local Parameters >>

” or“

Ethernet Remote 

Parameters >>

”; to enter you must press the 

 (Right) button.

As example, to select the address 12 for the ModBus protocol, the following procedure must be issued:

• Select the Communication menu“

COMMUNICATION >>

”.

• By means 

 (Down) button select the “

RS485 Protocol >>

”.

• Press the 

 (Right) button to enter; the following message is displayed: 

 “

Protocol MODBUS

 “

Address 1

 “

9600 baud

• Start the procedure to effect a change explained in the Setting modifying (SET) paragraph

• Press the 

 (Enter); button for a few seconds; the modifi cation in progress status is highlighted by 

the both START and TRIP flashing.

• Move the cursor over the parameter intended for change using the 

 (Enter), button, (in the exam-

ple on the 1 address),

• Change the parameters by means the 

 (increment) button (up to 12 address),

• Press the 

 (Enter) button to move the cursor over the last parameter in the display.

• Press the 

 (Enter) button once again; the cursor and the LED TRIP turn off (the LED START keeps 

flashing),

• Press the 

 (Enter) button for a few seconds; new message appears: “

Confirm settings?

• Answer to the message 

ENTER: YES

 to confirm changes or 

RESET: NO

 to abort.

The end of the LED blinking points out the end of procedure.

 

Circuit breaker commands

By means of the 

 (open) and 

 (close) keys, the circuit breaker commands may be issued.

The committed output relays must be enabled inside the 

Circuit Breaker supervision \

LEDs-relays allocation menu.

 

Note 1 Instantly all the relays are switched in rest state, including relays programmed as “normally energized”   

Содержание NVA100X

Страница 1: ...ing function please contact THYTRONIC TABLE OF CONTENTS Packaging 1 Contents 1 Technical support 1 INSTALLATION 2 Mounting 2 Flush mounting 2 I O diagram 4 Electrical connections 5 Output relays 6 Bin...

Страница 2: ...ns indicated in the overall dimensions drawing increased by 3 mm to ensure an adequate tolerance and gasket space between adjacent relays The depth dimension as indicated in the drawing must be increa...

Страница 3: ...started 01 2018 Remove the two vertical frames for access the holes for the fi xing screws the frames are snapped Insert the device into the slot Fit the device to the panel with four screws Replace t...

Страница 4: ...2 18 20 19 9 10 11 12 13 14 OC1E KC1 1 4 6 5 KC1 2 7 8 KC1 3 KC1 4 KC1 5 KC1 6 15 17 16 KC1 7 KC1 8 1 3 2 18 20 19 9 10 11 12 13 14 OC2F KC2 1 4 6 5 KC2 2 7 8 KC2 3 KC2 4 KC2 5 KC2 6 15 17 16 KC2 7 K...

Страница 5: ...r checks on the amperometric circuits is essential to provide appropriate support to achieve the secondary circuit shorting For security reasons it is advisable to operate in the absence of line curre...

Страница 6: ...1 5 mm2 for two conductors with same cross section Tightening torque 0 5 0 6 Nm Stripping length 10 mm Output relays The device may be confi gured with Two boards with eight command relays KC1 1 KC1 8...

Страница 7: ...ed by means ThySetter sw and local connection Set the IP address Host IP address and IP net mask n order that the NVA100X and PC parame ters are matched Set to OFF parameters Autonegotiation on relay...

Страница 8: ...le end It is recommended to terminate the line at the extremities of the same this must be performed on the RS485 line control unit and on the ProNext device placed at the furthest point serial1 sch a...

Страница 9: ...Press the key ENTER PASSWORD message is displayed followed by Password not ok press the key you can enter the personal password with the usual procedure de fault password is 0000 Press the Enter butt...

Страница 10: ...ameter from MMI can be changed and the changes can only be made by ThySetter To enable modification from MMI without password is needed to disable password lock connecting a PC with Thysetter setting...

Страница 11: ...possible faults blink lighted The display backlight is automatically activated when any key switch is set By means of the Up or Down buttons it is possible to cyclically browse through the menu option...

Страница 12: ...ower supply to the relay As example to set the operating mode of the KC1 1 output relay as ENERGIZED LATCHED the following procedure must be issued Select menu Set SET by mean of the button Down Press...

Страница 13: ...in menu till the RS485 Protocol Ethernet Local Parameters or Ethernet Remote Parameters to enter you must press the Right button As example to select the address 12 for the ModBus protocol the followi...

Страница 14: ...n 0 000 In IL 0 000 In ULmax 0 000 En UL 0 000 Un U 0 000 Un PhiL1 0 deg PhiL2 0 deg PhiL3 0 deg Alpha1 0 deg Alpha2 0 deg Alpha3 0 deg PhiE 0 deg PhiEC 0 deg DTheta 0 DThetaB I1 0 000 In I2 0 000 In...

Страница 15: ...BLK2IN DThAL2 OFF BLK2IN DThAL2 OFF BLK4IN DThAL2 OFF Trip DTh OFF BLK1 DTh OFF BLK2IN DTh OFF BLK4IN DTh OFF CLP DTh OFF 49LT 79 ActiveMode 79 OFF Run 79 OFF CycleState 79 Rest Residual time 79 0 s L...

Страница 16: ...K4IN IPD OFF Start IPD OFF Trip IPD OFF CLP IPD OFF BLK1 IPD OFF BLK2IN IPD OFF BLK4IN IPD OFF Start IPD OFF Trip IPD OFF CLP IPD OFF BLK1 IPD OFF BLK2IN IPD OFF BLK4IN IPD OFF 67 Start U OFF Trip U O...

Страница 17: ...000 Un U12r 0 000 Un U23r 0 000 Un U31r 0 000 Un IEr 0 000 IEn IECr 0 000 IEn UEr 0 000 UEn UECr 0 000 UECn PhiL1r 0 deg PhiL2r 0 deg PhiL3r 0 deg Alpha1r 0 deg Alpha2r 0 deg Alpha3r 0 deg PhiEr 0 deg...

Страница 18: ...D cnt 0 ParBk1IPD cnt 0 ParBk2IPD cnt 0 ParStIED cnt 0 ParTrIED cnt 0 ParBk1IED cnt 0 ParBk2IED cnt 0 ParStIED cnt 0 ParTrIED cnt 0 ParBk1IED cnt 0 ParBk2IED cnt 0 ParStIED cnt 0 ParTrIED cnt 0 ParBk1...

Страница 19: ...otBk2IPD cnt 0 TotStIPD cnt 0 TotTrIPD cnt 0 TotBk1IPD cnt 0 TotBk2IPD cnt 0 TotStIED cnt 0 TotTrIED cnt 0 TotBk1IED cnt 0 TotBk2IED cnt 0 TotStIED cnt 0 TotTrIED cnt 0 TotBk1IED cnt 0 TotBk2IED cnt 0...

Страница 20: ...16 IN2 1 0000000000000000 Relays KC1 8 KC1 1 00000000 Relays KC2 8 KC2 1 00000000 Fault x Cause No faults Operating phase Date Time IL1r 0 000 In IL2r 0 000 In IL3r 0 000 In UL1r 0 000 En UL2r 0 000 E...

Страница 21: ...tOFF 0 s IN1 2 matching None Logic Active ON ON Delay IN1 2 tON 0 s OFF Delay IN1 2 tOFF 0 s IN1 2 matching None ENABLE VECTOR JUMP Endphi ON 0 2 En tEndphi 0 5 s INPUTS IN1 1 IN1 16 Binary input IN1...

Страница 22: ...Common P1 Element P2 Element Q1 DIR Q Forward Q1 RES 0 00 s Q1 def enable OFF Q1 def 0 50 Qn tQ1 def 1 00 s Q1 BLK1 OFF Relays Q1 Q1 ST K Q1 TR K LEDs Q1 Q1 ST L Q1 TR L Q2 DIR Q Forward Q2 RES 0 00 s...

Страница 23: ...BLK4 OFF Dth BF OFF Dth disby50 51 OFF Relays Dth Dth K LEDs Dth Dth L Dth Element 49MG Common DthIN 0 0 DThetaB KST 2 0 K2 0 T 10 min T 1 0 T DthCLP Mode OFF tDthCLP 0 10 s DthAL1 Element DthAL1 Ena...

Страница 24: ...ILR inv 0 8 IB I MOT ST 1 IB tLR inv 10 s ILR BLK1 OFF ILR BLK2IN OFF ILR BLK2OUT OFF ILR BF OFF Relays ILR ILR ST K ILR TR K LEDs ILR ILR ST L ILR TR L ILR Enable OFF Mode51LR No speed crt1 tLRCLP 0...

Страница 25: ...U U ST K U TR K LEDs U U ST L U TR L U def Enable OFF U def 1 Un tU def 1 s U BLK1 OFF U disbyU OFF U BF OFF Relays U U ST K U TR K LEDs U U ST L U TR L Utype59 Uph ph Logic59 OR U Element U Element...

Страница 26: ...IEDCLP def 1 IEn tED def 1 s IED BLK1 OFF IED BLK2IN OFF IED BLK2OUT OFF IED BLK4 OFF IED BF OFF IED disIED OFF IED disIED OFF IED disIED OFF Relays IED IED ST K IED TR K LEDs IED IED ST L IED TR L IE...

Страница 27: ...LEDs BLOCK2IN tB L BLOCK2 INPUT ModeBLOUT1 OFF tF IPh 1 s tF IE 1 s tF IPh IE 1 s Relays BLOCK2OUT BLOCK2OUT IPh K BLOCK2OUT IE K BLOCK2OUT IPh IE K LEDs BLOCK2OUT BLOCK2OUT IPh L BLOCK2OUT IE L BLOC...

Страница 28: ...Protocol MODBUS Address 1 9600 bauds REMOTE TRIPPING PulseBLOUT1 OFF PulseBLIN1 OFF Relays PulseBLIN1 K LEDs PulseBLIN1 L PILOTE WIRE DIAGNOSTIC Test state OFF Stop test Yes Start test Yes Test KC1 1...

Отзывы: