FUNCTION CHARACTERISTICS
79
NA20 - Manual - 04 - 2022
Residual overcurrent - 50N/51N
Preface
Three operation thresholds, independently adjustable (
I
E
>,
I
E
>>,
I
E
>>>) with adjustable delay (
t
E
>,
t
E
>>,
t
E
>>>).
The first one (
I
E
>) may be programmed with definite or inverse time according the IEC and ANSI/IEEE
standard, as well as with EM curve.
The second and third thresholds (
I
E
>>,
I
E
>>>) with independent time.
For each threshold a reset time can be set (
t
E>RES
,
t
E>>RES
,
t
E>>>RES
) useful to reduce the clearing
time for intermittent faults.
The first threshold trip may be inhibited by start of the second and/or third threshold (
I
E
>>,
I
E
>>>).
Similarly the second threshold trip may be inhibited by start of the third threshold (
I
E
>>>).
Operation and settings
The residual fundamental frequency current is compared with the setting value. Current above the
associated pickup value is detected and a start is issued. After expiry of the associated operate time
a trip command is issued; if instead the current drops below the threshold, the element is restored.
The first threshold (
I
E
>) may be programmed with definite or inverse time according the following
characteristic curves:
• Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t
= 0.14 ·
t
E
>
inv
/ [(
I
E
/
I
E
>
inv
)
0.02
- 1]
• Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t
= 13.5 ·
t
E
>
inv
/ [(
I
E
/
I
E
>
inv
) - 1]
• Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t
= 80 ·
t
E
>
inv
/ [(
I
E
/
I
E
>
inv
)
2
- 1]
• Long Time Inverse (IEC 255-3/BS type B LTI):
t
= 120 ·
t
E
>
inv
/ [(
t
E
/
t
E
>
inv
) - 1]
• Moderately Inverse (ANSI/IEEE type MI):
t
=
t
E
>
inv
· {0.01 / [(
I
E
/
I
E
>
inv
)
0.02
- 1] + 0.023}
• Very Inverse (ANSI/IEEE type VI):
t
=
t
E
>
inv
· {3.922 / [(
I
E
/
I
E
>
inv
)
2
- 1] + 0.098}
• Extremely Inverse (ANSI/IEEE type EI):
t
=
t
E
>
inv
· {5.64 / [(
I
E
/
I
E
>
inv
)
2
- 1] + 0.024}
• Electromechanical (EM):
t
=
t
E
>
inv
· {0.28 / [-0236 · (
I
E
/
I
E
>
inv
)
-1
+ 0.339]}
Where:
t
:
operate time
I
E
>:
pickup value
t
E
>
inv
:
operate time setting
For all inverse time characteristics, following data applies:
• Asymptotic reference value (minimum pickup value): 1.1
I
E
>
• Minimum operate time: 0.1
s
• Range where the equation is valid:
[1]
1.1 ≤
I
E
/
I
E
>
inv
≤ 20
• If
I
E
>
inv
pickup ≥ 0.5
I
En
, the upper limit is 10
I
En
For all definite time elements the upper limit for measuring is 10
I
En
.
All residual overcurrent elements can be enabled or disabled by setting
ON
or
OFF
the
IE> En-
able
,
IE>> Enable
and/or
IE>>> Enable
parameters inside the
Set \ Profile A(or B) \ Residual
overcurrent-50N/51N \
IE> Element
(
IE>> Element
,
IE>>> Element) \ Setpoints
menus.
The first overcurrent element can be programmed with definite or inverse time characteristic by
setting the
IE>Curve
parameter (
DEFINITE, IEC/BS A, IEC/BS B, IEC/BS C, IEC/BS B LI,
ANSI/IEE MI, ANSI/IEE VI, ANSI/IEE EI, EM
) available inside the
Set \ Profile A(or B) \ Re-
sidual overcurrent-50N/51N \
IE> Element \ Setpoints
menu.
Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
t-int-F50N-51N.ai
I
E
I
E
>>
I
E
>>>
t
E
>
t
E
>>
t
E
>>>
I
E
>
t
TRIP
General operation time characteristic for the residual overcurrent elements - 50N/51N