MEASURES, LOGIC STATES AND COUNTERS
113
NA20 - Manual - 04 - 2022
• MID16-1 module Boot
OK/NOT OK
• MID16-1 module Run-time
OK/NOT OK
• MID16-2 module Boot
OK/NOT OK
• MID16-2 module Run-time
OK/NOT OK
• PT100 module Boot
OK/NOT OK
• PT100 module Run-time
OK/NOT OK
• Current loop module Boot
OK/NOT OK
• Current loop Run-time
OK/NOT OK
• Oscillography run-time
OK/NOT OK
The diagnostic alarms can be allocated to an output relay; for this purpose the
Self-test relay
pa-
rameter can be set (
K1...K6
) inside the
Set \ Self-test Relay
submenu.
Pilot wire diagnostic
Detailed diagnostic information about the pilot wire are available.
(
Read \ Pilot wire diagnostic
).
• BLIN1 pilot wire breaking diagnostic state
ON/OFF
• Pilot wire BLIN1 shorted
ON/OFF
Selective Block - BLOCK2
The input and output state concerning the selective block are available (
Read \ Selective block-
BLOCK2
).
Block2 input
• Phase protections input selective block state
BLK2IN-Iph
ON/OFF
• Ground protections input selective block state
BLK2IN-IE ON/OFF
• tB-Iph/IE Elapsed state
tB timeout
ON/OFF
Block2 output
• Starting state of phase protections enabled
for external selective block on output
ST-Iph-BLK2
ON/OFF
• Starting state of ground protections enabled
for external selective block on output
ST-IE-BLK2
ON/OFF
• Phase protections output
selective block state
BLK2-OUT-Iph
ON/OFF
• Ground protections
output selective block state
BLK2-OUT-IE
ON/OFF
• Phase and ground protections
output selective block state
BLK2-OUT-Iph/IE
ON/OFF
Fault recording - SFR
Recording is triggered by one or more causes (up to 8 simultaneous):
• Activation (OFF-ON transition) of any relay programmed for trip of protection or control element
• External trigger (binary input programmed as
Fault trigger
)
Twenty events are recorded into a circular FIFO (First In, First Out) buffer.
[1][2]
Following information are stored in every record:
• Fault counter
[3]
• Date and time
• Fault cause (element trip)
• Phase currents
I
L1r
,
I
L2r
,
I
L3r
• Residual current
I
Er
• Thermal image
Dtheta
-
r
• Negative sequence current
I
2r
• Negative sequence current/positive sequence current ratio (
I
2
/
I
1
)
r
• Inputs IN1-IN5
• Outputs K1-K6
• Fault cause info (eg. faulted phase)
Event recording - SER
Recording is triggered by one or more causes:
• Start and/or trip of any enabled protection or control element
• Binary input activation (OFF-ON or ON-OFF transition)
• Power-on or power-down (Auxiliary power supply)
• Setting change.
Three hundred events are recorded into a circular FIFO (First In, First Out) buffer.
[2][4]
Following information are stored in every record:
• Event counter
[5]
• Date and time
• Event cause (binary input/output relay/setting changes)
Note 1 Fault 0 is the newest fault, while the Fault 19 is the oldest fault
Note 2 Data are stored into non-volatile memory; they are is retained once power is turned off.
Note 3 Counter is updated at any new record; it may be cleared by means ThyVisor
Note 4 Event 0 is the newest event, while the Event 299 is the oldest event
Note 5 Counter is updated at any new record; it may be cleared by means ThyVisor