EAP 110 

 

ANNUNCIATOR 

 

 

INSTALLATION, OPERATING & 

SERVICE MANUAL 

 

 

 
 

 

 

 

PM058  Rev 2 06/01/18

 

 

 

9087A – 198

th

 Street, Langley, BC Canada V1M 3B1     Telephone (604) 888-0110 

Telefax (604) 888-3381     E-Mail: [email protected]     www.thomsontechnology.com

 

Содержание EAP 110

Страница 1: ...IATOR INSTALLATION OPERATING SERVICE MANUAL PM058 Rev 2 06 01 18 9087A 198 th Street Langley BC Canada V1M 3B1 Telephone 604 888 0110 Telefax 604 888 3381 E Mail info thomsontechnology com www thomson...

Страница 2: ...TACT INPUTS 7 2 4 REMOTE COMMUNICATION WIRING 7 2 5 ANNUNCIATOR CONTROL WIRING 8 2 6 ANNUNCIATOR LOCATION INSTALLATION 8 3 DESCRIPTION 11 3 1 LEXAN FACEPLATE 11 3 2 PRINTED CIRCUIT BOARD 12 4 OPERATIN...

Страница 3: ...ATOR 8 ANNUNCIATOR LABELS 22 8 1 NFPA 110 LABELS 22 8 2 CSA 282 LABELS 23 8 3 MEC 20 GROUP 2 FAULT LABELS 24 8 4 MEC 2 GROUP 2 FAULT LABELS 25 9 TROUBLE SHOOTING 26 10 NOTES 27 PM058 Rev2 06 01 18 Tho...

Страница 4: ...GENERAL DESCRIPTION The EAP 110 annunciator is designed for remote fault annunciation of emergency standby generator sets utilizing Thomson Technology MEC 2 MEC 20 Engine Controllers The design uses a...

Страница 5: ...ilding code standards for Emergency Standby Generator systems CAUTION contents subject to damage by STATIC ELECTRICITY This equipment contains static sensitive parts Please observe the following anti...

Страница 6: ...The battery DC negative or common conductor must be grounded to the main generator set frame ground The EAP 110 is internally protected by a solid state type fuse that protects it from inadvertent sh...

Страница 7: ...be voltage free i e dry contact The use of a powered contact will damage the Annunciator 2 4 REMOTE COMMUNICATION WIRING All interconnecting wiring to from the EAP 110 Annunciator communication port...

Страница 8: ...ower 14 AWG 2 5mm2 2 5 2 External Fault Contacts 16 AWG 1 5mm2 2 5 3 Remote Communication Wiring 22 AWG 0 34mm2 8 Conductor Shielded Cable For distances exceeding 1000 Ft 300m consult THOMSON TECHNOLO...

Страница 9: ...from front faceplate 3 0 EAP 110 Rear Cover 1 0 FIGURE 1 6 50 7 0 7 0 0 25 6 50 4 Faceplate Mounting Holes 3 16 DIAMETER EAP 110 FLUSH MOUNTING G ENGINEER PRODUCTS EAP110 Flush Mount VSD 0 25 Enclosur...

Страница 10: ...Assembly G ENGINEER PRODUCTS EAP110 Assembly VSD Side View Wall Edge Flush Mounting Wall Edge Surface Mounting EAP Front Faceplate EAP Flush Mounting Plate optional EAP 110 Rear Cover FIGURE 3 PM058 R...

Страница 11: ...tdown EPS Supplying Load Low Engine Temperature Alarm Loss of Speed Signal Shutdown High Engine Temperature Alarm High Engine Temperature Shutdown Weak Battery Voltage Low Battery Voltage High Battery...

Страница 12: ...nal block is provided for DC control power ground and 4 external contact inputs Refer to the connection diagram in section 7 for further information 3 2 2 COMMUNICATION PORT One RJ45 communication por...

Страница 13: ...MEC 20 Engine controller as required NFPA 110 level 2 CSA 282 FIGURE 6 Indicates the specific fault addressing for Group 1 faults The EAP 110 will be supplied from the factory set for Group 1 address...

Страница 14: ...utdown or External Input 4 Low Oil Pressure Alarm Overspeed Shutdown Overcrank Shutdown EPS Supplying Load Low Engine Temperature Alarm Loss of Speed Signal Shutdown High Engine Temperature Alarm High...

Страница 15: ...r input devices if programmed accordingly Refer to the engine controller instruction manual for further information DATE 06 01 24 Power On Communication Fail Spare Digital Fault 5 Spare Digital Fault...

Страница 16: ...lt LED lights D19 D20 as shown in FIGURE 8 may be programmed for input from either two different alarm address inputs when the annunciator is set for group 1 addressing With JP3 jumper ON the EAP 110...

Страница 17: ...hts D11 D12 as per FIGURE 8 will be activated when set for Group 1 addressing 2 The EAP will be supplied from the factory with JP3 OFF i e to address to the analog LOP HET faults Alarm Silence Power O...

Страница 18: ...fault condition has been reset at the engine controller If the EAP 110 is also connected to the 4 possible external contact input circuits these faults will be activated in the same sequence by the r...

Страница 19: ...ram LED D1 s horn function momentarily press the LAMP TEST push button The flashing rate of the LED will change to reflect the different settings The two different flashing rates indicate the followin...

Страница 20: ...sted cable 1000 ft Max Plug in RJ45 Connector EXTERNAL CONTACT INPUT Close to DC Negative TEMPERATURE RANGE 40 C to 50 Deg C ENVIRONMENTAL Faceplate NEMA 12 Rear Enclosure NEMA 1 DIMENSIONS 6 0 W x 6...

Страница 21: ...n GRD M EC 2 20 Engine Controller J6 12 24V Engine Cranking Battery B B 8 conductor Shielded Tw isted Cable c w RJ45 connectors Communication cable w iring must be suitably routed to protect it from s...

Страница 22: ...and straight edge cut into 4 vertical strips at crop marks Insert each strip into the correct lexan slot centering text in windows Emergency Stop EPS Supplying Load EPS Switch Not In Auto Digital Fau...

Страница 23: ...witch Not In Auto Digital Fault 1 Overcrank Shutdown Low Engine Temperature Alarm Weak Battery Voltage Digital Fault 2 Overspeed Shutdown Loss of Speed Signal Shutdown Low Battery Voltage Low Coolant...

Страница 24: ...s Under Voltage Shutdown Progr 6 Digital Fault 12 Digital Fault 8 Over Voltage Shutdown Digital Fault 5 Over Current Alarm Digital Fault 9 Under Frequency Shutdown Over Frequency Shutdown High Engine...

Страница 25: ...t each strip into the correct lexan slot centering text in windows Under Voltage Shutdown Progr 6 Over Voltage Shutdown Over Current Alarm Under Frequency Shutdown Over Frequency Shutdown High Engine...

Страница 26: ...up even with correct DC power applied Check that there are no wiring errors short circuits connected to the Annunciator Note The EAP 110 contains an electronic fuse that triggers upon an overload con...

Страница 27: ...cable is connected to the MEC Expansion Port J6 and not the communication port J7 2 MEC 2 applications require software version 1 2 or greater software version for correct EAP 110 operation Annunciato...