background image

IS---0366

IS---K656DR

September 2010

Page 1 of 3

Installation/Operating Instructions

K656DR

Deadbreak Insulated Cap with Test Point

CONTENTS: Insulated Cap, Lubricant (Do Not Substitute), Stud (if applicable), Installation Instructions.

The K656DR is designed for insulating, shielding and watersealing any ELASTIMOLD 15kV class (8.3kV phase--to--ground) and

25kV class (15.2 kV phase--to--ground) 600 amp deadbreak bushing interface.

DANGER

All apparatus must be de--energized during installation

or removal of part(s). For loadbreak products follow

operating instructions. All deadbreak connectors must

be de--energized before operating. All 200A deadbreak

connectors must be mechanically secured with bails

when connected.
All apparatus must be installed and operated in

accordance with individual user, local, and national

work rules. These instructions do not attempt to provide

for every possible contingency.
Do not touch or move energized products.
Excess distortion of the assembled product may result

in its failure.

Inspect parts for damage, rating and compatibility with

mating parts.
This product should be installed only by competent

personnel trained in good safety practices involving

high voltage electrical equipment. These instructions

are not intended as a substitute for adequate training or

experience in such safety practices.
Failure to follow these instructions will result in damage

to the product and serious or fatal injury.
If this product is supplied with a protective shipping

cover(s), remove this shipping cover(s) and replace with

the appropriate HV insulated cap(s) or connector(s)

before submerging or energizing the circuit.

FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.

IMPORTANT

1. Check contents of package to ensure they are complete

and undamaged.

2. Check all components to ensure proper fit with cable

and/or mating products.

3. Read entire installation instructions before starting.

4. Have all required tools at hand and maintain cleanliness

throughout the procedure.

Installing The Insulating Cap

STEP 1

Insert a length of No. 14 AWG ( 2.5mm

2

) copper wire (or

equivalent) through the grounding eye of the insulated cap.

Make a small loop and twist tight, taking care not to damage the

grounding eye. Connect free end of grounding wire to the

system ground using a suitable connector. Length of grounding

wire should be sufficient for the distance from the grounding

point to the grounding eye of the insulated cap when installed.

If the bushing is not equipped with a stud, hand assemble the

stud supplied into the insulated cap. If the bushing is equipped

with a stud, discard the stud supplied.

No. 14 Copper

Grounding Wire

To Ground

Stud (Where Applicable)

STEP 2

In new installations, where the bushing is known to be

de--energized, thoroughly wipe the bushing interface and the

insulated cap interface clean of all contaminants. Lubricate

above surfaces with the supplied lubricant or Elastimold

approved lubricant. On circuits previously energized, clean and

lubricate

only

the interface of the insulated cap.

Clean and Lubricate

Bushing Interface

Apparatus

IS---0366

IS---K656DR

September 2010

Printed in U.S.A.

8155 T&B Boulevard, Memphis, Tennessee 38125

(800) 888--0211 Fax: (800) 888--0690