TI120 Series Variable Frequency Drive
Detailed parameter introduction
- 77 -
Chapter 5 Detailed parameter introduction
P00 frequency given parameter
P00.00
Main given digital setting of
frequency
range:0.00Hz~upper limit
frequency
Factory
default:50.00Hz
P00.01
Main given mode of frequency
range:0~C
Factory default:0
0: Digital given P00.00+Up/Down adjustment
1: Analog input AI1
2: Analog output AI2
Analog AI1 input specification:0~10V and 0~20mA,Can be selected by dialing code on the control
panel,Analog AI2 input specification:0~10V
。
The corresponding relationship between the analog input
and the given frequency is defined by the P12 group.
3: Reserve
4: Min[AI1,AI2]
Take the minimum value of analog input AI1, AI2 as the frequency setting source,The output
frequency is limited by the upper and lower limits.
5: Max[AI1,AI2]
The maximum value of the analog input AI1, AI2 given as the frequency setting source, the output
frequency is limited by the upper and lower limits.
6: Sub[AI1,AI2]
Using [AI1-AI2] as the frequency setting source, the output frequency is limited by the upper and
lower limits.
7: Add[AI1,AI2]
Using [AI1+AI2] as the frequency setting source, the output frequency is limited by the upper and
lower limits.
8: Pulse given HDI
Receive high-speed pulse signal through terminal X7/HDI,As a frequency setting method, the
correspondence between HDI and frequency is determined by P12.33~P12.36 function codes.
9: Process PID
The result output by the process PID operation is used as the frequency setting source, please refer
to the P40 group parameter function code for details.
A: Simple PLC
The control output of the simple PLC is used as the frequency setting source, please refer to the
P42 group parameter function code for details.
B: Keyboard potentiometer
The keyboard panel with a potentiometer can be used to adjust the frequency.
C: No given
The main given frequency output is 0