TI120 Series Variable Frequency Drive
System Installation and Wiring
- 10 -
motor cable is more than 100m, an AC output reactor must be installed near the variable
frequency drive.
5)
Grounding terminal
● Terminals must be reliably grounded and the resistance of grounding wire must be less than
10Ω. Otherwise, the equipment will work abnormally or even be damaged.
● Do not share the grounding terminal
with the N terminal of the neutral line of the power
supply.
●
The impedance of the protective grounding conductor must meet the requirement of
withstanding short-circuit large current in case of failure.
● The size of the protective grounding conductor shall be selected according to the following
table.
2.3.5 Control unit
1)
Control unit layout
Figure 2-5 Control Unit
The sectional area (S) of a stage line
Minimum sectional Area (Sp) of protective
conductors
S ≤ 16mm
2
S
16mm
2
<
S ≤ 35mm
2
16mm
2
35mm
2
<
S
S/2