background image

 

8  

 

WARNING! 

Make sure all the DC connections are tight (torque to 9-10 
ft-lbs, 11.7-13Nm). Loose connections will overheat and could 
result in a potential hazard. 

 

2-4-4  Before proceeding further, carefully check that cable you have just connected negative 

terminal of inverter to the negative output power source. 

 

2-4-5  Connect the cable from the positive terminal of the inverter to the positive terminal of the 

power source. Make a secure connection. 

 

2-4-6  Set the power switch to the ON position; you will hear the “bi-bi-bi” sound, then the 

inerter comes into standby state.   

 

2-4-7  Set the power switch to the OFF position; the device shuts down completely. 

 

2-4-8  Please use a power meter to accurately measure the true output R.M.S. voltage of 

inverter. 

Our company uses a power meter such as IDRC CP-350 or ABM 2019 to measure our 

product. 

 

 

2-5  AC Safety Grounding 

There is an acrylic plate in front of the terminals of AC input and output. Before connecting the 

AC source and load, please remove the plate. 

 

During the AC wiring installation, AC input and output ground wires are connected to the inverter.       

The AC input ground wire must connect to the incoming ground from your AC utility source. 

The AC output ground wire should go to the grounding point for your loads (for example, a 

distribution panel of ground bus) 

 

 

CAUTION! 

Reverse polarity connection will blow a fuse in inverter and 
may permanently damage the inverter.
Damage caused by reversing polarity connection is not 
covered by our warranty. 

 

WARNING! 

You may observe a spark when you make this connection 
since current may flow to charge capacitors in the power 
inverter.  
Do not make this connection in the presence of flammable 
fumes. Explosion or fire may result.

 

YOUR CONNECTION TO SAFETY

Thiele KG 

• V
orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

[email protected] 

• www

.thiele-kg.de

Thiele KG 

• V

orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

[email protected] 

• www

.thiele-kg.de

YOUR CONNECTION TO SAFETY

klick to

www

u-s-v

YOUR CONNECTION TO SAFETY

klick to

www

ACDC-DCDC

YOUR CONNECTION TO SAFETY

klick to

www

SYSTEME

YOUR CONNECTION TO SAFETY

klick to

www

CONTACT

YOUR CONNECTION TO SAFETY

klick to

www

CALLBACK

Содержание PST700w Series

Страница 1: ...info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YOUR CONNECTION TO SAFETY klick to www...

Страница 2: ...afety precautions 13 6 2 Precautions when working with batteries 13 7 Appendices A 7 1 110VAC Dip switch 14 7 2 220VAC Dip switch 14 YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Ba...

Страница 3: ...hen appliances microwave ovens refrigerators and freezers coffee makers blenders ice markers toasters 1 1 5 Industrial equipment metal halide lamp high pressure sodium lamp 1 1 6 Home entertainment el...

Страница 4: ...0 1 0 Protection Overload Short Circuit Reverse Polarity fuse Input Undervoltage Input Overvoltage Over Temperature LED Light On Line By Pass Power OLP UVP OVP OTP Safety EN60950 1 2006 IEC60950 1 200...

Страница 5: ...e kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YOUR CONNECTION TO SAFETY klick to www u s v YOUR CONNECTION TO SA...

Страница 6: ...Undervoltage Overvoltage Protection OTP on Over Temperature Protection 2 1 4 AC input and output connector WARNING Do not connect the AC source to the inverter s AC output terminal do not connect AC l...

Страница 7: ...l safety hazard WARNING Shock Hazard Before proceeding further carefully check the inverter is NOT connected to any batteries and that all wiring is disconnected from any electrical sources Do not con...

Страница 8: ...and prolonged exposure that will damage the inverter 2 4 Quick Hook Up and Testing 2 4 1 Unpack and inspect the power inverter check to see that the power switch in the OFF position 2 4 2 There is an...

Страница 9: ...ng installation AC input and output ground wires are connected to the inverter The AC input ground wire must connect to the incoming ground from your AC utility source The AC output ground wire should...

Страница 10: ...ndards requires us to test and recommend specific GFCI Our company has tested the following GFCI protected 20A receptacles and found that they functioned properly when connected to the output of the i...

Страница 11: ...warranty Model No Wire AWG Inline Fuse YK PST1270 YK PST1270E 4 100A YK PST2470 YK PST2470E 6 50A YK PST4870 YK PST4870E 8 30A YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Backnan...

Страница 12: ...ceeded 12V 24V 48VDC version Ref point 2 7 1 2 7 3 Under Voltage Protection indicator UVP The under voltage indicator indicates that the power inverter has shut itself down because its input voltage f...

Страница 13: ...l shock or fire Problem and Symptom Possible Cause Solution Low output voltage 110V 95 105VAC 220V 190 210VAC Using average reading voltmeter Use true RMS reading meter and cable Ref point 2 4 7 Load...

Страница 14: ...reduce risk of hazard do not cover or obstruct the ventilation openings Do not install the inverter in a zero clearance compartment Overheating may result 6 1 2 To avoid a risk of fire and electronic...

Страница 15: ...Q Hz S2 S3 BAUD RATE S4 S5 VOLTAGE OUTPUT VAC ON 60 OFF OFF 2400 OFF OFF 200 OFF 50 OFF ON 4800 OFF ON 220 ON OFF 9600 ON OFF 230 ON ON 19200 ON ON 240 S1 FREQ Hz 50Hz 60Hz S2 S3 BAUD RATE 2400 4800 9...

Отзывы: