2-4-5  Set  the  power  switch  to  the ON  position;  you  will  hear  the 

bi-bi-bi

  sound.  At  the  same 

time,  the  display  shows  the  word 

ASIAN

  for  two  times.  After  that,  you  will  hear  the 

continuous  sound  from  internal  alarm.  Then,  the  AC  voltage  shows  on  the  display.  It 
means the device has done the operation. 

 
2-4-6  Set the power switch to the OFF position; the device shuts down completely. 

 

2-4-7  Please  use  a  power  meter  to  accurately  measure  the  true  output  R.M.S.  voltage  of 

inverter. 
Our  company  uses  a  power  meter  such  as  IDRC  CP-350  or  ABM  2019  to measure  our 
product. 

 

 

 

2-5  AC Safety Grounding: 

The  AC  output  ground  wire  should  go  to  the  grounding  point  for  your  loads  (for  example,  a 
distribution panel ground bus). 
 

2-5-1  Neutral g

rounding (GFCI’s):

 

2-5-1.1 

120V Models:

 

The  neutral  conductor  of  the  AC  output  circuit  of  the  inverter  is  automatically 
connected to the safety ground during inverter operation.  According  to National 
Electrical  Code  requirements  that  separately  derived  AC  sources  (such  as 
inverter and generators) have their neutral conductors tied to ground in the same 
way  that  the  neutral  conductor  from  the  utility  is  tied  to  ground  at  the  GFCI 
breaker panel. For models configured with a transfer relay, while AC utility power 
is presenting and the inverter is in bypass mode, this connection (neutral of the 

inverter’s AC output to input safety ground) is not present so that the utility 

neutral is only connected to ground at your breaker panel, as required. 
 

2-5-1.2 

230V Models: 

 

There is no connection made inside the inverter from either the line or neutral 
conductor to the safety ground. 

 

Ground Fault Circuit Interrupters (GFCI’S):

 

Installations in Recreational Vehicles (for North American approvals) will require GFCI 
protection of all branch circuit connected to the AC output of the hardwire terminal 
equipped inverter. In addition, electrical codes require GFCI protection of certain 
receptacles in residential installations. While the pure sine wave output of the inverter is 
equivalent to the waveform provided by utilities, compliance with UL standards requires us 
to test and recommend specific GFCI. Our company has tested the following 
GFCI-protected 20A receptacles and found that they functioned properly when connected 
to the output of the inverter. 

YOUR CONNECTION TO SAFETY

Thiele KG 

• V
orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

[email protected] 

• www

.thiele-kg.de

Thiele KG 

• V

orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

[email protected] 

• www

.thiele-kg.de

YOUR CONNECTION TO SAFETY

klick to

www

u-s-v

YOUR CONNECTION TO SAFETY

klick to

www

ACDC-DCDC

YOUR CONNECTION TO SAFETY

klick to

www

SYSTEME

YOUR CONNECTION TO SAFETY

klick to

www

CONTACT

YOUR CONNECTION TO SAFETY

klick to

www

CALLBACK

Содержание Asian Electron PSW1500W Series

Страница 1: ...0 19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YOUR CONNECTION TO SAFETY klick to...

Страница 2: ...tions 17 6 2 Precautions when working with batteries 17 7 Appendices A 7 1 Dip switch 18 7 2 Tune VR 18 8 Appendices B 8 1 Powering saving mode 18 YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg...

Страница 3: ...ncandescent lights shavers sewing machines 1 1 4 Kitchen appliances microwave ovens refrigerators and freezers coffee makers blenders ice markers toasters 1 1 5 Industrial equipment metal halide lamp...

Страница 4: ...Polarity fuse Input Undervoltage Input Overvoltage Over Temperature Digital Display OVP UVP OTP OLP VAC AMP WATT VDC TEMP Hz Safety EN60950 1 EMC FCC Class B EN55022 2010 AC 2011 Class B EN55024 2010...

Страница 5: ...40A 0 40A 0 20A Stand by Current Draw 1 5W Power Saving Mode Output Waveform R Load Pure Sine Wave 3 THD Protection Overload Short Circuit Reverse Polarity Fuse Input Undervoltage Input Overvoltage Ov...

Страница 6: ...thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YOUR CONNECTION TO SAFETY klick to www u s v YOUR CONNECTION...

Страница 7: ...t will display various status on the function screen such as VAC Amp watts and so on When malfunction is occurred its display will be flashed on the screen YOUR CONNECTION TO SAFETY Thiele KG Vorderer...

Страница 8: ...and may damage inverter permanently YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG V...

Страница 9: ...inberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info...

Страница 10: ...engine compartments 2 3 4 Ventilated Allow at least 3 inch of clearance around the inverter for airflow Ensure the ventilation openings on the rear and bottom of the unit are not obstructed 2 3 5 Dust...

Страница 11: ...output power source CAUTION Reverse polarity connection will blow a fuse in inverter and may permanently damage the inverter Damage caused by reversing polarity connection is not covered by our warra...

Страница 12: ...ction neutral of the inverter s AC output to input safety ground is not present so that the utility neutral is only connected to ground at your breaker panel as required 2 5 1 2 230V Models There is n...

Страница 13: ...drop WARNING The installation of a fuse must be on positive cable Failure to place a fuse on cables running between the inverter and battery may cause damage to the inverter and will void warranty In...

Страница 14: ...m the power inverter turn them on separately after the inverter has been turned on This will ensure that the power inverter does not have to deliver the starting currents for all the loads at once YOU...

Страница 15: ...W220200 YK PSW220200E 275VDC 270VDC 185VDC 180VDC 2 7 2 Output Voltage indicator LED displays light on VAC as show as output voltage value 2 7 3 Output Current indicator LED displays light on AMP as s...

Страница 16: ...r has shut itself down because its temperature has become overheated The power inverter may overheat because it has been operated at power levels above its rating or because it has been installed in a...

Страница 17: ...hooting Guide WARNING Do not open or disassemble the inverter Attempting to service the unit yourself may result in a risk of electrical shock or fire Problem and Symptom Possible Cause Solution Low o...

Страница 18: ...that existing wiring is in good electrical condition and that wire size is not undersized Do not operate the inverter with damaged or substandard wiring 6 2 Precautions When Working with Batteries 6 2...

Страница 19: ...watts the inverter shuts down the output power Only essential systems are kept alive to reduce power consumption from the batteries to a very low value of only about 1 5 watts As soon as a load is swi...

Отзывы: