INTRODUCTION
In your own interest of safety, gas appliances should be installed by competent persons.
Failure to install the appliance correctly could invalidate any warranty or liability claims.
This appliance shall be installed in accordance with the manufacturers installation
instructions, local gas fitting regulations, municipal building codes, AG5601 and any other
relevant statutory regulations.
Data label.
The data label is located on the right hand side front of the oven compartment, behind the
oven door. A duplicate data label is supplied to adhere to an accessible area next to the
appliance. Ensure that the gas supply is Propane. This appliance is designed for use with
Propane gas and should not be converted for use with any other gas.
Provision of Ventilation
The use of a gas cooking appliance results in a production of heat and moisture in a room
in which it is installed. Ensure that the kitchen is well ventilated and in accordance with
AG5601 Installation Code. In general, the appliance should have adequate ventilation for
complete combustion of gas, proper flueing and to maintain temperature of immediate
surroundings within safe limits.
Location
This appliance maybe installed in a kitchen/kitchen diner but NOT in a room containing a
bath or a shower. LP gas appliances must not be fitted below ground level. e.g. in a
basement.
Choose a location free of draughts, open doors and clear of combustible materials and
other fire hazards. The location should ensure convenience of operation and service. Any
adjoining wall surface situated within 200mm from the edge of any hob burner must be
made from a suitable non-combustible material for a height of 150mm for the entire length
of the hotplate.
IMPORTANT
•
This appliance must be installed into an aperture, sealed off at either side in
order to prevent draughts from adjoining cupboards/vents. Ensure that air vents
and gas escape holes are kept clear, holes for cables and pipes must be sized to
minimize air leakage between compartments.
•
Under no circumstances should the ventilation hole exceed 3850mm
2
or other
low level ventilation be located in the compartment, including vents in kickboards.
Low level vents in adjacent compartments are permitted.
4