6. 

Complete  with  1  additional  pass  of  heat 

reflective tape.

Heat Reflective Tape

Glass Fiber Tape

Heat Tracing

7. 

Cut FAK-1 top and base ends to match outside 

diameter  of  tubing  bundle  and  remove  end 

pieces.

Tubing

RTD

11

.

 

For HPT and FP cable, exchange grommet in 

Terminator with GRW-GT2 provided in PETK-

3-ECM.

GRW-GT2

GRW

RTD

Tubing Bundle

Cut and Remove 

to fit

Heat Tracing

Field Drilled 

(By Others)

O-Ring

Expediter 

Base

Mount Screw 

and Washers

Weep Hole

FAK-1 Base

8. 

Mount expediter base with o-ring to FAK-1 base 

using (3) M5 mounting screws and lock washers. 

Punch out weep hole.

Silicone

 

Gasket

9. 

Install RTV silicone and gasket, cutting off excess. 

Apply RTV sealant to both halves.

Drilled hole 

for bundle 

entry

Drilled holes 

for securing 

FAK-1

Drilled holes for 

securing FAK-1

Use as template

14. 

Field drill required entry hole in wall/plate. Use 

the FAK-1 flange as a template and mark and 

drill holes for bolts. 

12. 

Apply self-vulcanizing tape around bundle jacket 

and work up over FAK ends.

Expediter Base

Heat Tracing

RTD

FAK-1 

Bottom Cover

FAK-1 

Top Cover

13. 

Terminate heat tracing with appropriate PETK 

termination  kit.  Refer  to  PETK  installation 

instructions for details (not addressed here).

RTD

Power Connection 

Boot

Heat Tracing

Ground Braid

10. 

Assemble FAK-1 top, tubing bundle, and FAK-1 

bottom together as shown Snap together firmly. 

Inspect ends of tubing splice cover for snug fit. 

Apply additional RTV sealant where needed.

TraceNet

TM

 ECM/FAK-1