Controller operating manual
15.11.2020 – Version 1.1
TCS.2 series –
thermofin
®
control system 2
nd
generation
Page: 44/162
Operating manual - translation into English © thermofin GmbH
* Factory setting
Analogue IN basic unit
Possible configuration
Pressing the right arrow button enables the following functions to be selected:
Input
Terminal
Possible functions
AI – 1
(X4.29)
Pressure sensor 1 (4-20 mA)
Outlet sensor 1 (resistance KTY 81-210)
Ambient sensor (resistance KTY 81-210)
Room sensor (resistance KTY 81-210)
Conductivity 1 (4-20 mA)
Current sensor of lift motor 1 (0-10 V)
Not used
AI – 2
(X4.30)
Pressure sensor 2 (4-20 mA)
Outlet sensor 2 (resistance KTY 81-210)
Inlet sensor 1 (resistance KTY 81-210)
Ambient sensor (resistance KTY 81-210)
Coil sensor (resistance KTY 81-210)
Current sensor of lift motor 2 (0-10 V)
Conductivity 2 (4-20 mA)
Feedback of 3-way valve (0-10 V)
Current sensor of lift motor 2
Not used
AI – 3
(X4.31)
Pressure sensor 3 (4-20 mA)
Inlet sensor 1 (resistance KTY 81-210)
Ambient sensor (resistance KTY 81-210)
Drip tray sensor (resistance KTY 81-210)
Setpoint shifting 1 (see chap. 4.2.4)
Speed slave 1 (0-10 V, see chap. 4.2.5)
Current sensor of lift motor 3 (0-10 V)
Humidity sensor (4-20 mA)
Not used
AI – 4
(X4.32)
Pressure sensor 4 (4-20 mA)
Inlet sensor 2 (resistance KTY 81-210)
Ambient sensor (resistance KTY 81-210)
Cell sensor (resistance KTY 81-210)
Setpoint shifting 2 (see chap. 4.2.4)
Speed slave 2 (0-10 V, see chap. 4.2.5)
Current sensor of lift motor 4 (0-10 V)
Humidity sensor (4-20 mA)