Refrigeration Maintenance (Rev. 04/03)
95
Set Up and Test of Evacuation Equipment
NOTE: Refer to the previous two pages for the following
discussion.
1.
Connect the evacuation system to a 110 Vac power
supply. Connect a gauge manifold and refrigerant
supply to the fitting above valve V-4. Turn the micron
gauge ON.
2.
Close valves V-1, V-3 and V-4. Valve V-2 is open.
3.
Turn the vacuum pump ON.
4.
Open valve V-1 at the pump. The micron gauge needle
will move to the left. (Refer to micron gauge scale
diagram—previous page.)
LEAK
Isolate the pump from the system by closing the
proper valve. Watch the movement of the vacuum
gauge needle. If the needle continues to rise, this is an
indication that a leak exists in the unit or the connect-
ing line. The leak must then be located and eliminated.
NOTE: If the vacuum pump is okay, and there are no
leaks between V-1 and V-3, the micron gauge should
show less than 500 microns. If not, locate and correct
the problem.
5.
With the pump still operating, open valve V-3. If the
micron reading does not return to a level of less than
500 microns, locate and correct the problem before
continuing.
6.
With the vacuum pump still operating, open valve V-4.
The micron level will rise momentarily. If the micron
reading does not return to a level of less than
500 microns, locate and correct the problem before
continuing.
MOISTURE
Should the needle show a pressure rise but finally
level off to practically a constant mark, this is an indi-
cation that the system is vacuum tight but is still too
wet, requiring additional dehydration and pumping
time.
Содержание KD-II SR
Страница 4: ......
Страница 8: ......
Страница 13: ...Safety Precautions Rev 04 03 v AEA40...
Страница 14: ...Safety Precautions Rev 04 03 vi AEA38...
Страница 33: ...Unit Description Rev 04 03 19 1 Evaporator 2 Access Door Rear View Curbside KD II SR 1 2 AEA38...
Страница 37: ...Unit Description Rev 04 03 23 Power Receptacle Box KD II SR 50 AEA42...
Страница 38: ...Unit Description Rev 04 03 24 1 Keypad 2 LED Display THERMOGUARD Remote Control Panel AEA43 1 2...
Страница 42: ...P T System Description Rev 04 03 28 High Voltage Tray No Options High Voltage Tray with Phase Correction...
Страница 44: ...P T System Description Rev 04 03 30 High Voltage Tray with Single Phase Power and Electric Heater...
Страница 58: ...Remote Control Panel Features Rev 04 03 44...
Страница 112: ...Refrigeration Maintenance Rev 04 03 98...
Страница 120: ...106...
Страница 146: ...132...
Страница 156: ...142...
Страница 162: ...148...
Страница 170: ...156...
Страница 172: ...158...
Страница 173: ...159 KD II 30 Schematic Diagram Page 1 of 2...
Страница 174: ...160 KD II 30 Schematic Diagram Page 2 of 2...
Страница 175: ...161 KD II 30 Wiring Diagram Page 1 of 2...
Страница 176: ...162 KD II 30 Wiring Diagram Page 2 of 2...
Страница 177: ...163 KD II 50 Schematic Diagram Page 1 of 2...
Страница 178: ...164 KD II 50 Schematic Diagram Page 2 of 2...
Страница 179: ...165 KD II 50 Wiring Diagram Page 1 of 2...
Страница 180: ...166 KD II 50 Wiring Diagram Page 2 of 2...
Страница 181: ...167 KD II 50 SR 230 1 60 Wiring Diagram Page 1 of 2...
Страница 182: ...168 KD II 50 SR 230 1 60 Wiring Diagram Page 2 of 2...