MP-3000a Controller
104
Code
Description
Corrective Action
22
Total Current Too Low (Alarm)
• Compressor Start-up: unit or component
current draw is 50% below expected amps for
4 minutes.
• Indicates:
• Defective or open fuse CB 7A
• Defective or open high pressure cutout
switch
• Defective evaporator high temperature
protection switch
• Defective or open motor internal high
temperature protection switch
• Unit on water-cooled condensing with no
water flow
• Defective condenser coil sensor or sensor
locations
• Check LCD display for High Pressure Cutout
message.
• Enter Manual FUnction Test menu and test
(operate) each component. Check volts and
amps to determine which component has low
amp draw.
• Check volt and ampere meter.
23
Supply Air Temperature Too High (Check
Alarm)
• During Chill or Frozen Mode: Supply air
temperature is too high compared to return
air temperature under operating conditions.
• Indicates:
• Low refrigerant charge
• Incorrect connection or location of supply
or return air sensor
• Air leakage at supply air sensor cable
• Ice or frost on evaporator coil
• Incorrect evaporator fan operation
• Check discharge an suction pressure gauge
readings and refrigerant charge.
• Check for sensor or evaporator fan alarm codes.
• Open evaporator door. Inspect coil for ice or
frost and initiate manual defrost if necessary.
Check for correct evaporator fan motor rotation
and operation.
• Check supply and return sensor connections
and locations.
Содержание CRR-40 119
Страница 4: ......
Страница 16: ...Safety Precautions 16...
Страница 18: ...Service Guide 18...
Страница 20: ...Model Features 20...
Страница 32: ...Specifications 32...
Страница 120: ...MP 3000a Controller 120...
Страница 160: ...Wiring and Schematic Diagrams Index 160...
Страница 161: ...161 MPC2000 Wiring Schematic...
Страница 162: ...162 MPC2000 High Voltage Wiring Diagram...
Страница 163: ...163 MPC2000 Low Voltage Wiring Diagram...
Страница 164: ...164 MPC2000 WCC Wiring Schematic...