Operating Instructions
84
Manual Emergency Mode
Operation
In the event of an emergency situation where a
failure of the controller occurs, a manual
emergency mode function can be used to operate
the unit. However, the unit must be manually
cycled on and off using the unit 460/380V main
circuit breaker. This is because manual control
disconnects both the controller and
U
NIT
O
N
/O
FF
switch from the main relay board. Manual control
offers a selection of six operating positions:
Position 1:
Not Use:
Position 2:
Cool: Continuous cooling with
condenser fan in operation, compressor in
operation, vapor injection in operation, and
evaporator fan high in operation.
Position 3:
Not Used
Position 4:
Not Used
Position 5: Defrost:
Heaters are activated
(evaporator fans off).
Position 6: Evaporator Fan:
Evaporator fans
operate at high speed to introduce fan motor heat
only into the container (no electric heater
operation).
To select Manual Control:
1. Turn the
U
NIT
O
N
/O
FF
switch to
O
FF
.
2. Turn the unit 460/380V main circuit breaker
off. Then disconnect the unit power cord from
the power supply.
Figure 44: Manual Emergency Control Connections
3. Disconnect cable No. 2 from the controller
and main relay board (see electrical
schematic). The main relay board will now
control the unit based on the manual control
setting.
NOTE: MUST check 2-pin plug location on
J501 connections of main relay board to ensure
correct unit operation.
4. If necessary, remove 2-pin plug from J501
(see decal on main relay board) and relocate
based on the unit operating mode required.
5. Connect the unit power cord to the proper
power supply.
6. Start the unit by turning the unit 460/380V
main circuit breaker on.
NOTE: On MAGNUM units, both the
460/380V main circuit breaker and the Unit
On/Off switch must be used to cycle the unit
on and off. The Unit On/Off switch must be
On to operate the scroll compressor.
7. Check for correct rotation of condenser fan.
Condenser air should be blowing out from the
center of the grille. If the fan is running
backwards, power supply phase must be
changed.
CAUTION: The unit must be cycled on
and off manually to maintain the desired
temperature. Use the 460/380V main
circuit breaker to start and stop the unit.
Monitor container temperature with an
external thermometer.
WARNING: The unit will automatically
start and operate if 460/380V power is
present at the main relay board when the
controller is disconnected. To prevent
personal injury from rotating machinery
or dangerous electrical shock from high
voltage controls, disconnect the supply
power to the unit before preparing the unit
for manual emergency mode operation.
AJA1843
Содержание 098916
Страница 2: ...MAGNUM TK 51122 4 MM Rev 6 02 06 Copyright 2004 Thermo King Corp Minneapolis MN USA Printed in USA...
Страница 5: ......
Страница 11: ...Table of Contents 10...
Страница 19: ...Service Guide 18...
Страница 28: ...Specifications 27 Figure 2 Physical Specifications AMA313...
Страница 41: ...Unit Description Features Options 40...
Страница 105: ...Operating Instructions 104...
Страница 155: ...Servicing The Unit 154...
Страница 187: ...Index 186...
Страница 189: ...Wiring and Schematic Diagrams Index 188...
Страница 190: ...189 Wiring Schematic...
Страница 191: ...190 Wiring Diagram Page 1 of 2...
Страница 192: ...191 Wiring Diagram Page 2 of 2...